User-Programmable Pushbuttons - GE D30 Instruction Manual

Line distance
Hide thumbs Also See for D30:
Table of Contents

Advertisement

5.2 PRODUCT SETUP
PATH: SETTINGS
PRODUCT SETUP
USER PUSHBUTTON 1
5
Twelve (12) optional user-programmable pushbuttons (specified in the order code) provide an easy and error-free method
of entering digital state (on, off) information. The digital state can be entered locally (by directly pressing the front panel
pushbutton) or remotely (via FlexLogic™ operands) into FlexLogic™ equations, protection elements, and control elements.
Typical applications include breaker control, autorecloser blocking, and setting groups changes. The user-programmable
pushbuttons are under the "Control" level of password protection.
The user-configurable pushbuttons are shown below. They can be custom labeled with a factory-provided template, avail-
able online at http://www.GEmultilin.com.
5-38

USER-PROGRAMMABLE PUSHBUTTONS

PUSHBUTTON 1
FUNCTION: Disabled
PUSHBTN 1 ID TEXT:
MESSAGE
PUSHBTN 1 ON TEXT:
MESSAGE
PUSHBTN 1 OFF TEXT:
MESSAGE
PUSHBTN 1 SET:
MESSAGE
Off
PUSHBTN 1 RESET:
MESSAGE
Off
PUSHBTN 1 AUTORST:
MESSAGE
Disabled
PUSHBTN 1 AUTORST
MESSAGE
DELAY: 1.0 s
PUSHBTN 1 REMOTE:
MESSAGE
Off
PUSHBTN 1 LOCAL:
MESSAGE
Off
PUSHBTN 1 DROP-OUT
MESSAGE
TIME: 0.00 s
PUSHBTN 1 LED CTL:
MESSAGE
Off
PUSHBTN 1 MESSAGE:
MESSAGE
Disabled
PUSHBUTTON 1
MESSAGE
EVENTS: Disabled
D30 Line Distance Relay
5.2.12 USER-PROGRAMMABLE PUSHBUTTONS
USER PUSHBUTTON 1(12)
Range: Self-Reset, Latched, Disabled
Range: Up to 20 alphanumeric characters
Range: Up to 20 alphanumeric characters
Range: Up to 20 alphanumeric characters
Range: FlexLogic™ operand
Range: FlexLogic™ operand
Range: Disabled, Enabled
Range: 0.2 to 600.0 s in steps of 0.1
Range: FlexLogic™ operand
Range: FlexLogic™ operand
Range: 0 to 60.00 s in steps of 0.05
Range: FlexLogic™ operand
Range: Disabled, Normal, High Priority
Range: Disabled, Enabled
5 SETTINGS