Power shutdown and magnetic contactor (MC)

 Inverter input side magnetic contactor (MC)
On the inverter input side, it is recommended to provide an MC for the following purposes. (Refer to
• To disconnect the inverter from the power supply at activation of a protective function or at malfunctioning of the driving
system (emergency stop, etc.).
For example, an MC prevents overheat or burnout of the brake resistor when heat capacity of the resistor is insufficient or
brake regenerative transistor is damaged with short while connecting an optional brake resistor.
• To prevent any accident due to an automatic restart at power restoration after an inverter stop made by a power failure.
• To separate the inverter from the power supply to ensure safe maintenance and inspection work.
To use an MC to perform an emergency stop during operation, select the MC by applying the inverter's input-side current
to the rated current specified in the JEM1038-AC-3 class.
NOTE
• Since repeated inrush currents at power ON will shorten the life of the converter circuit (switching life is about 1,000,000 times),
frequent starts and stops of the magnetic contactor must be avoided. Turn ON or OFF the start (STF/STR) signal for the
inverter start control to run or stop the inverter.
• Inverter start/stop circuit example
As shown in the following figure, always use the start signal (turn ON or OFF the STF/STR signal) to make a start or stop.
Operation preparation
OFF
ON
MC
Start/Stop
MC
Start
Stop
RA
*1
When the power supply is 400 V class, install a stepdown transformer.
*2
Connect the power supply terminals R1/L11, S1/L21 of the control circuit to the input side of the MC to hold an alarm signal when the inverter's
protective circuit is activated. At this time, remove jumpers across terminals R/L1 and R1/L11 and S/L2 and S1/L21. (Refer to
of the jumper.)
 Handling of the magnetic contactor on the inverter's output side
Switch the magnetic contactor between the inverter and motor only when both the inverter and motor are at a stop. When the
magnetic contactor is turned ON while the inverter is operating, overcurrent protection of the inverter and such will activate.
When an MC is provided to switch to a commercial power supply, for example, it is recommended to use the electronic bypass
function Pr.135 to Pr.139 (refer to
dedicated motors (SF-V5RU, SF-THY) nor with PM motors.)
126
3. PRECAUTIONS FOR USE OF THE INVERTER
3.4 Power shutdown and magnetic contactor (MC)
MCCB
MC
Power
supply
∗1
T
MC
RA
RA
page
532). (The commercial power supply operation is not available with Vector control
U
R/L1
To the
motor
V
S/L2
W
T/L3
R1/L11
∗2
S1/L21
Inverter
C1
B1
A1
STF/STR
SD
page 29
for selection.)
page 76
for removal

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fr-a820-00167 (2.2k)Fr-a820-00046-gf (0.4k)Fr-a820-00250 (3.7k)Fr-a820-00105-gf (1.5k)Fr-a820-00077 (0.75k)Fr-a820-00250-gf (3.7k) ... Show all

Table of Contents