CHAPTER 4: SETPOINTS
ELEMENT
OPERANDS
Breaker Failure
BF1 Retrip
BF1 Highset OP
BF1 Lowset OP
BF1 52b Superv OP
BF1 OP
BF 2, BF 3
Breaker Health
BKR1 Hlth PKP
BKR1 Hlth Trip PKP
BKR1 Hlth Cls PKP
BKR1 Hlth Chg PKP
BKR1 Arc PKP A
BKR1 Arc PKP B
BKR1 Arc PKP C
BKR1 Engy PKP A
BKR1 Engy PKP B
BKR1 Engy PKP C
BKR1 Hlth OP Fail
BKR1 Arc Fail
BKR1 Charge Fail
Breaker 2 Health, Breaker 3 Health
Breaker
BKR1 Opened
BKR1 Closed
BKR1 Unkwn State
BKR1 Disconnected
BKR1 Connected
BKR2 to BKR 3
Close Circuit Monitoring Cls Coil Mon 1 PKP
Cls Coil Mon 1 OP
Contact Inputs
CI # On
CI # Off
Critical Failure Relay
Critical Fail OP
Demand
Current Dmd PKP
Current Dmd PKP A
Current Dmd PKP B
Current Dmd PKP C
RealPwr Dmd PKP
ReactvPwr Dmd PKP
ApprntPwr Dmd PKP
Digital Counters
Counter 1 HI
Counter 1 EQL
Counter 1 LO
Counter 1 at Limit
Counter 2 to Counter 16
Directional Power
DirPwr 1 Stg1 PKP
DirPwr 1 Stg2 PKP
DirPwr 1 PKP
DirPwr 1 Stg1 OP
DirPwr 1 Stg2 OP
DirPwr 1 OP
DirPwr 2
Frequency Rate-Of-
FreqRate1 PKP
Change
FreqRate1 OP
FreqRate1 Up PKP
FreqRate1 Up OP
FreqRate1 Dwn PKP
FreqRate1 Dwn OP
FlexElements
FlexEl 1 PKP
FlexEl 1 OP
FlexEl 2 to 8
845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
EVENT DESCRIPTION
Breaker failure 1 re-trip operated
Breaker failure 1 operated with high level current supervision (includes
breaker status supervision if set)
Breaker failure 1 operated with low level current supervision (includes
breaker status supervision if set)
Breaker failure 1 operated with breaker status only
Breaker failure 1 operated
Same set of operands as for BF 1
Breaker health has picked up
Trip time of breaker health has picked up
Close time of breaker health has picked up
Spring charge time of breaker health has picked up
Arc time of phase A of breaker health has picked up
Arc time of phase B of breaker health has picked up
Arc time of phase C of breaker health has picked up
Arc energy of phase A of breaker health has picked up
Arc energy of phase B of breaker health has picked up
Arc energy of phase C of breaker health has picked up
Breaker trip or close operation has failed
Breaker arc time has failed
Spring charge time has failed
Same set of operands as for Breaker Health 1
Breaker state is detected opened
Breaker state is detected closed
Close or Open breaker state cannot be detected
Breaker has been detached from the power system
Breaker has been racked-in the power system
Same set of ooperands as for BKR 1
Close Coil 1 Monitoring element has picked up.
Close Coil 1 Monitoring element has operated for an amount of time
greater than the Close Circuit Monitor Pick-up Delay Time.
# – any contact input number
The critical failure relay operated
At least one phase from current demand element has picked up
Phase A from current demand element has picked up
Phase B from current demand element has picked up
Phase C from current demand element has picked up
Real power demand has picked up
Reactive power demand has picked up
Apparent power demand has picked up
Digital counter 1 output is 'more than' comparison value
Digital counter 1 output is 'equal to' comparison value
Digital counter 1 output is 'less than' comparison value
Digital counter 1 reached limit
Same set of operands as for Counter 1
Stage 1 of the directional power element 1 has picked up
Stage 2 of the directional power element 1 has picked up
The directional power element has picked up
Stage 1 of the directional power element 1 has operated
Stage 2 of the directional power element 1 has operated
The directional power element has operated
The same set of operands per DirPwr 1
The frequency rate of change 1 element has picked up
The frequency rate of change 1 element has operated
The frequency rate of change 1 element has picked up on raising
frequency
The frequency rate of change 1 element has operated on raising
frequency
The frequency rate of change 1 element has picked up on lowering
frequency
The frequency rate of change 1 element has operated on lowering
frequency
The FlexElement 1 has picked up
The FlexElement 1 has operated
The FlexElements 2 to 8 is the same as Flexelement.
FLEXLOGIC
4–321