GE D90 Plus Communications Manual page 211

Line distance protection system
Hide thumbs Also See for D90 Plus:
Table of Contents

Advertisement

CHAPTER 3: DNP COMMUNICATION
Object 50 (time and date)
Object 52 (time delay)
Object 60 (class 0, 1, 2, and 3 data)
PLUS
D90
LINE DISTANCE PROTECTION SYSTEM – COMMUNICATIONS GUIDE
06 (no range, or all)
07, 08 (limited quantity)
17, 28 (index)
The following codes are used for responses.
Function codes for responses, object 34, variations 1, 2, and 3:
129 (response)
Qualifier codes for responses, object 34, variations 1, 2, and 3:
00, 01 (start-stop)
17, 28 (index)
Object 50, variation 1: time and date
Variation 1 is used to request the default variation. The following codes are used for
requests.
Function codes for requests, object 50, variation 1:
1 (read)
2 (write)
Qualifier codes for requests, object 50, variation 1:
00, 01 (start-stop)
06 (no range, or all)
07 (limited quantity, quantity = 1)
08 (limited quantity)
17, 28 (index)
The following codes are used for responses.
Function codes for responses, object 50, variation 1:
129 (response)
Qualifier codes for responses, object 50, variation 1:
00, 01 (start-stop)
17, 28 (index)
Object 52, variation 2: time delay fine
There are no codes used for requests.
The following codes are used for responses.
Function codes for responses, object 52, variation 2:
129 (response)
Qualifier codes for responses, object 52, variation 2:
07 (limited quantity, quantity = 1)
Object 60, variation 0: class 0, 1, 2, and 3 data
The following codes are used for requests.
Function codes for requests, object 60, variation 0:
1 (read)
20 (enable unsolicited response)
DNP DEVICE PROFILE