Advertisement

5 SETTINGS
!
PATH: SETTINGS
PRODUCT SETUP
# FLEX STATE
# PARAMETERS
MESSAGE
MESSAGE
This feature provides a mechanism where any of 256 selected FlexLogic™ operand states can be used for efficient moni-
toring. The feature allows user-customized access to the FlexLogic™ operand states in the relay. The state bits are packed
so that 16 states may be read out in a single Modbus register. The state bits can be configured so that all of the states
which are of interest to the user are available in a minimum number of Modbus registers.
The state bits may be read out in the "Flex States" register array beginning at Modbus address 900 hex. 16 states are
packed into each register, with the lowest-numbered state in the lowest-order bit. There are 16 registers in total to accom-
modate the 256 state bits.
!
PATH: SETTINGS
PRODUCT SETUP
# USER-DEFINABLE
# DISPLAYS
# USER DISPLAY 1
#
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
# USER DISPLAY 2
#
# USER DISPLAY 8
#
GE Multilin
!"

FLEX STATE PARAMETERS

PARAMETER
1:
Off
PARAMETER
2:
Off
PARAMETER 256:
Off
!"

USER-DEFINABLE DISPLAYS

DISP 1 TOP LINE:
DISP 1 BOTTOM LINE:
DISP 1 ITEM 1
0
DISP 1 ITEM 2
0
DISP 1 ITEM 3
0
DISP 1 ITEM 4
0
DISP 1 ITEM 5:
0
C60 Breaker Management Relay
5.2.11 FLEX STATE PARAMETERS
Range: FlexLogic™ Operand
Range: FlexLogic™ Operand
Range: FlexLogic™ Operand
5.2.12 USER-DEFINABLE DISPLAYS
Range: up to 20 alphanumeric characters
Range: up to 20 alphanumeric characters
Range: 0 to 65535 in steps of 1
Range: 0 to 65535 in steps of 1
Range: 0 to 65535 in steps of 1
Range: 0 to 65535 in steps of 1
Range: 0 to 65535 in steps of 1
5.2 PRODUCT SETUP
5
5-21