System Configuration; Connecting To Slmp Equipment - Mitsubishi Electric GOT2000 Series Connection Manual

Graphic operation terminal microcomputers, modbus/fieldbus products, peripherals
Hide thumbs Also See for GOT2000 Series:
Table of Contents

Advertisement

8.2 System Configuration

8.2.1

Connecting to SLMP equipment

SLMP equipment
Communication
Controller
Type
Cable model
• 1000BASE-T
100BASE-TX
Shielded twisted
pair cable (STP)
or unshielded
twisted pair cable
(UTP) of category
SLMP
Ethernet
5 or higher
equipment
• 10BASE-T
Shielded twisted
pair cable (STP)
or unshielded
twisted pair cable
(UTP) of category
3 or higher
*1
Connect the GOT to the SLMP equipment via a hub.
Use cables, connectors, and hubs that meet the IEEE802.3 10BASE-T/100BASE-TX/1000BASE-T standards.
*2
When connecting GT2000 to an equipment that meets the 10BASE (-T/2/5) standard, use the switching hub and operate in an
environment where 10Mbps and 100Mbps can be mixed.
*3
A length between a hub and a node.
The maximum distance differs depending on the Ethernet device to be used.
The following shows the number of the connectable nodes when a repeater hub is used.
• 10BASE-T: Max. 4 nodes for a cascade connection (500m)
• 100BASE-TX: Max. 2 nodes for a cascade connection (205m)
When switching hubs are used, the cascade connection between the switching hubs has no logical limit for the number of
cascades.
For the limit, contact the switching hub manufacturer.
*4
Use the straight cable.
*5
For details, refer to the SLMP equipment manual.
Connection cable
Connection cable
External
Maximum
device
*4
segment
*3
length
*1
100m
Hub
Hub
Connection cable
Connection cable
Maximum
4
segment
Cable model*
*3
length
• 1000BASE-T
100BASE-TX
Shielded twisted
pair cable (STP) or
unshielded twisted
pair cable (UTP) of
category 5 or
higher
100m
• 10BASE-T
Shielded twisted
pair cable (STP) or
unshielded twisted
pair cable (UTP) of
category 3 or
higher
8. SLMP CONNECTION

8.2 System Configuration

GOT
*2
GOT
Number of
connectable
Option
GOT
equipment
device
model
When SLMP
equipment:GOT
is N:1
The number of
SLMP
equipment for 1
GOT is TCP:
128 or less.
When SLMP
- (Built
equipment:GOT
into GOT)
is 1:N
The following
shows the
number of GOTs
for 1 SLMP
equipment
Depends on the
SLMP
equipment
*5
used.
8
8 - 3