Connecting Multiple Rs485 Devices - Siemens RUGGEDCOM RX1501 Installation Manual

Hide thumbs Also See for RUGGEDCOM RX1501:
Table of Contents

Advertisement

Chapter 3
Communication Ports
1
2
3
Figure 51: Installing a Module
1. Module
2. Chassis
5.
Install a new module or a blank module (to prevent the ingress of dust and dirt). For more information, refer
to
Section 3.9.2, "Removing a
6.
If necessary, install the device in the rack.
7.
Connect power to the device.
Section 3.10

Connecting Multiple RS485 Devices

Each RS485 port can communicate with multiple RS485 devices by wiring devices together in sequence over a
single twisted pair with transmit and receive signals on the same two wires (half duplex). For reliable, continuous
communication, adhere to the following guidelines:
• To minimize the effects of ambient electrical noise, use shielded cabling.
• The correct polarity must be observed throughout a single sequence or ring.
• The number of devices wired should not exceed 32, and total distance should be less than 1219 m (4000 ft) at
100 kbps.
• The Common terminals should be connected to the common wire inside the shield.
• The shield should be connected to earth ground at a single point to avoid loop currents.
• The twisted pair should be terminated at each end of the chain.
The following shows the recommended RS485 wiring.
34