FLEXLOGIC
Operand type
PASSWORD
SECURITY
RxGOOSE
RESETTING
SELF-DIAGNOSTICS
5
(See Relay Self-tests
descriptions in
Chapter 7:
Commands and
Targets)
TEMPERATURE
MONITOR
USER-
PROGRAMMABLE
PUSHBUTTONS
Some operands can be re-named. These are the names of the breakers in the breaker control feature, the ID (identification)
of contact inputs, the ID of virtual inputs, and the ID of virtual outputs. If the user changes the default name or ID of any of
these operands, the assigned name appears in the relay list of operands. The default names are shown in the FlexLogic
operands table.
The characteristics of the logic gates are tabulated in the following table, and the operators available in FlexLogic are
listed in the FlexLogic operators table.
5-122
Operand syntax
ACCESS LOC SETG OFF
ACCESS LOC SETG ON
ACCESS LOC CMND OFF
ACCESS LOC CMND ON
ACCESS REM SETG OFF
ACCESS REM SETG ON
ACCESS REM CMND OFF
ACCESS REM CMND ON
UNAUTHORIZED ACCESS
RxGOOSE 1 On
RxGOOSE 2 On
RxGOOSE 3 On
RxGOOSE 32 On
RxGOOSE 1 Off
RxGOOSE 2 Off
RxGOOSE 3 Off
RxGOOSE 32 Off
RESET OP
RESET OP (COMMS)
RESET OP (OPERAND)
RESET OP (PUSHBUTTON)
ANY MAJOR ERROR
ANY MINOR ERROR
ANY SELF-TESTS
BATTERY FAIL
CLOCK UNSYNCHRONIZED
DIRECT DEVICE OFF
DIRECT RING BREAK
EQUIPMENT MISMATCH
FLEXLOGIC ERR TOKEN
LATCHING OUT ERROR
MAINTENANCE ALERT
FIRST ETHERNET FAIL
PROCESS BUS FAILURE
PTP FAILURE
RxGOOSE OFF
RRTD COMM FAIL
SECOND ETHERNET FAIL
THIRD ETHERNET FAIL
SNTP FAILURE
SYSTEM EXCEPTION
TEMP MONITOR
UNIT NOT PROGRAMMED
TEMP MONITOR
PUSHBUTTON 1 ON
PUSHBUTTON 1 OFF
ANY PB ON
PUSHBUTTON 2 to 12
Operand description
Asserted when local setting access is disabled
Asserted when local setting access is enabled
Asserted when local command access is disabled
Asserted when local command access is enabled
Asserted when remote setting access is disabled
Asserted when remote setting access is enabled
Asserted when remote command access is disabled
Asserted when remote command access is enabled
Asserted when a password entry fails while accessing a password protected
level of the C30
Flag is set, logic=1
Flag is set, logic=1
Flag is set, logic=1
Flag is set, logic=1
Flag is set, logic=1
Flag is set, logic=1
Flag is set, logic=1
Flag is set, logic=1
Reset command is operated (set by all three operands below)
Communications source of the reset command
Operand (assigned in the INPUTS/OUTPUTS  RESETTING menu) source of
the reset command
Reset key (pushbutton) source of the reset command
Any of the major self-test errors generated (major error)
Any of the minor self-test errors generated (minor error)
Any self-test errors generated (generic, any error)
The battery is not functioning. Replace as outlined in the Maintenance
chapter.
Relay is not synchronized to the international time standard
A direct device is configured but not connected
The Direct I/O settings is for a connection that is not in a ring
The configuration of modules does not match the stored order code
A FlexLogic equation is incorrect
A difference is detected between the desired and actual latch contact state
A subset of the minor self-test errors generated, see Chapter 7
Link failure detected. See description in Chapter 7: Commands and Targets.
See description in Chapter 7: Commands and targets
"Bad PTP Signal" self-test as described in Chapter 7
One or more GOOSE messages are not being received
See description in Chapter 7: Commands and Targets
See description in Chapter 7: Commands and Targets
See description in Chapter 7: Commands and Targets
SNTP server is not responding
See description in Chapter 7: Commands and Targets
Monitors ambient temperature and maximum operating temperature
The product SETUP > INSTALLATION > RELAYS SETTINGS setting is not
programmed
Asserted while the ambient temperature is greater than the maximum
operating temperature (80°C)
Pushbutton number 1 is in the "On" position
Pushbutton number 1 is in the "Off" position
Any of 12 pushbuttons is in the "On" position
Same set of operands as PUSHBUTTON 1
C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL