CHAPTER 5: SETTINGS
"Latest/On" freezes the input in case of lost connectivity. If the latest state is unknown, such as after UR power-up
but before the first communication, the input defaults to logic 1. When communication resumes, the input
becomes fully operational.
"Latest/Off" freezes the input in case of lost connectivity. If the latest state is unknown, such as after UR power-up
but before the first communication, the input defaults to logic 0. When communication resumes, the input
becomes fully operational.
RxGOOSE Boolean1 EVENTS
Range: Disabled, Enabled
Default: Disabled
This setting selects whether Off to On transitions of the RxGOOSE Boolean1 FlexLogic operand are recorded by the event
recorder. If set to Enabled, Off to On transitions are recorded. On to Off transitions are not recorded, even if events are
enabled.
RxGOOSE DPS inputs
Navigate to Settings > Product Setup > Communications > IEC 618560 > GOOSE > RxGOOSE > RxGOOSE DPS Inputs >
RxGOOSE DPS1 to access the settings for the first RxGOOSE Boolean. The settings and functionality for the others are
similar.
RxGOOSE DPS1 ID
Range: 0 to 12 characters
Default: RxG DPS1
This setting allows the user to assign descriptive text to the names of the four RxGOOSE DPS1 FlexLogic operands. The
full operand name is the value of this setting appended with "Intermediate," "On," "Off," or "Bad." This descriptive text
also appears in the SCL files associated with the C30.
RxGOOSE DPS1 RxGOOSE
Range: None, RxGOOSE1, RxGOOSE2, and so on
Default: None
This setting selects the RxGOOSE containing the value that drives the RxGOOSE DPS1 FlexLogic operand. If set to None,
the RxGOOSE DPS1 FlexLogic operand assumes its default state.
C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL
Figure 5-15: RxGOOSE DPS Inputs panel
PRODUCT SETUP
5
5-51