Pf612 Ras Information - Toshiba 2000 User Manual

Integrated controller
Hide thumbs Also See for 2000:
Table of Contents

Advertisement

Chapter 8 RAS Information

8.3 PF612 RAS information

The address is the offset address (word address) from the beginning of the PF612 interface
memory.
(1) PF module status
F
0000h ONL
8
ONL
PF_MODE
NPR
(2) Healthy counter
F
0001h
Indicates that the PF module is operating normally. A 16-bit counter that is updated every
100 ms.
Returns to 0 after FFFFh.
38
PF612 RAS information is referenced with READ instruction.
Table 8-24 PF612 RAS information
Address
15
0000h
PF module status (1W)
0001h
Healthy counter (1W)
Indicates the status of the modules installed on the local unit.
Table 8-25 PF module status
E
D
C
B
A
PF_MODE
(ON LINE)
(PF_MODE)
(NO_PARA)
Indicates the normal operating status of the PF module.
Table 8-26 Healthy counter
E
D
C
B
A
9
8
7
6
NPR
1 : PF module is online
00: PF module is online
01: PF is standby
10: PF module is not operating
11: PF is down
1: No activation request
9
8
7
6
Healthy Counter
model 2000 PROFIBUS Module User's Manual for S2T/S2E
0
5
4
3
2
1
0: Not online
0: Activation request
5
4
3
2
1
0
0

Advertisement

Table of Contents
loading

Table of Contents