(a) Global error bit
Indicates the PF module internal transmission control error status.
7
6
Reserved(0)
No data
Auto clear
Control
(b) Master state
7
Value
00h
40h
80h
C0h
(c) Error remote address
7
00h to FEh
FFh
6F8C1147
Table 8-6 Global error bit
5
4
3
2
No data Auto clear
1: 1 or more remote node is not exchanging data or is in error
0: Operating normally
1: Running in auto clear mode due to remote node error
0: Operating normally
1: Parameter error occurred
0: Operating normally
6
5
4
3
Master state
Table 8-7 Master state
Name
OFFLINE
Offline
STOP
Data transmission with slave stopped
CLEAR
Input information from slave is read, but
output is cleared or retained
OPERATE
Cyclic data I/O is performed
Table 8-8 Error remote address
6
5
4
3
Err_Rem_Addr
Lowest no. of slave node which has an error
Master module internal error
8.1 PF611 RAS information
1
0
Control
2
1
0
State
2
1
0
8