Toshiba 2000 User Manual page 48

Integrated controller
Hide thumbs Also See for 2000:
Table of Contents

Advertisement

Chapter 8 RAS Information
(2) Healthy counter
F
0001h
Indicates that the PF module is operating normally. A 16-bit counter that is updated every
100 ms.
Returns to 0 after FFFFh.
(3) Device error
F
0002h
The error status is indicated with the following codes:
8
(4) PROFIBUS-DP status
Address
0010h
0011h
0012h
0013h
0018h
0020h
0028h
32
Indicates the normal operating status of the PF module.
Table 8-3 Healthy counter
E
D
C
B
A
Indicates the transmission module error status.
E
D
C
B
A
Error No.
Symbol
0
-
14
50
RAM_TEST
53
FLASH_TEST
100-107
SYSTEM
200
Unknown_IRQ
201
Watchdog
202
TX_IRQ
203
RX_IRQ
252
Download active
253
Bootloader active
Indicates the transmission module operating status.
Table 8-5 PROFIBUS-DP status
15
Master status
Error event
Bus error counter
Timeout counter
Slave setting status (bit for each slave)
Slave operating status (bit for each slave)
Slave diagnostic (bit for each slave)
9
8
7
6
5
Healthy Counter
9
8
7
6
5
Device Error
Table 8-4 Device error
No error
OS module, firmware download in progress
RAM check error
FLASH PROM checksum error
Internal system error
Unknown interrupt detected
Watchdog timer error
Unknown send interrupt from serial channel detected
Unknown receive interrupt from serial channel detected
Firmware or database download in progress
Bootstrap loader activeFirmware stopped
Global error bit
Error causing remote address
model 2000 PROFIBUS Module User's Manual for S2T/S2E
4
3
2
1
4
3
2
1
Description
0
0
0

Advertisement