Starting Of Defrost Operations; Completion Of Defrosting Operations; Control Of Liquid Level Detecting Heater; Judgement Of Refrigerant Amount - Mitsubishi Electric PUHY-200YMF-C Service Handbook

Air conditioners city multi
Table of Contents

Advertisement

2 PURY-(P)200·250YMF-C
1)

Starting of defrost operations

• After integrated 43 minutes of compressor operations, defrosting operations start when –8˚C : P-YMF-C, –6˚C :
YMF-C or less of piping temperature (TH7) is detected for 3 consecutive minutes.
• Forcible defrosting operations start by turning on forcible defrost switch (SW2-7) if 3 minutes have already elapsed
after compressor start or completion of defrosting operations.
2)

Completion of defrosting operations

Defrosting operations stop when 10 minutes have passed since start of defrosting operation, or piping temperature
(TH5) reaches 8˚C or more.
(Defrosting operations do not stop for 4 minutes after starting, except when piping temperature exceeds (TH5 and
TH7) 20˚C and Pd >10kg/cm
3)
Defrosting prohibition
Defrosting operations do not start during oil recovery, and for 10 minutes after starting compressor.
4)
Trouble during defrosting operations
When trouble is detected during defrosting operations, the defrosting operations stop, and defrosting prohibition
time decided by integrated operation time of compressor is set to be 20 minutes.
5)
Change in number of operating indoor units during defrosting operations
• In case number of operating indoor units changes during defrosting operations, the defrosting operations continue,
and control of unit number change is performed after the defrosting operations are finished.
• Even in case all indoor units stop or thermostat is turned off during defrosting operations, the defrosting operations
do not stop until expected defrosting activities are completed.

(8) Control of liquid level detecting heater

Detect refrigerant liquid level in accumulator, and heat refrigerant with liquid level heater for judging refrigerant
amount. 6 steps of duty control is applied to liquid level heater depending on frequency and outdoor air temperature,
1minute after starting compressor.

(9) Judgement of refrigerant amount

LD : Liquid level Detected Switch
2
G (0.98MPa).)
Inlet
LD2
Float
LD1
LD1 ON
LD1 OFF
Outlet
AL=2
AL=1
AL=0
Oil return
LD2 OFF
AL=1
AL=0
–61–
LD2 ON
AL=2