Basic Configuration of the Lambdatronic P 3200
Keys, Display and Operating Statuses
2.2 Operating statuses
There are 12 different boiler statuses, which are shown at the top left of the graphic display:
Preparation
Heating up
Pre-heating
Ignition
Heating
Constant burn
Cleaning
Shutdown wait
Shutdown wait 1
Shutdown wait 2
Fault
Burner Off
Fröling Heizkessel- und Behälterbau Ges.m.b.H
Tel +43 (0) 7248 606-0
Fax +43 (0) 7248 606-600
The boiler is ventilated, the sealing slider is opened and the Lambda probe
is heated.
The combustion chamber is filled with pellets.
The fan-assisted ignition switches on and the pellets are preheated until a
bed of embers is formed. For this period loading is deactivated.
The pellets are ignited with the fan-assisted ignition. The flame is
distributed around the whole combustion chamber. The control of the
loading unit is defined as "Ignition" in the parameter menu.
The Lambdatronic controls combustion according to the boiler setpoints.
The boiler has no power consumption. The ID fan and the loading unit are
deactivated.
The Lambdatronic carries out the cleaning program (duration approx. 3
min).
The grate and heat exchanger are cleaned.
When the boiler is interrupted during the heating up procedures (heating
up, pre-heating, ignition), it waits for a specified period of time until the next
start attempt.
The ID fan runs to burn the remaining pellets.
The loading unit is deactivated.
The system is still ventilated by chimney draught. The loading unit is
deactivated.
CAUTION - Fault persists!
Procedure see page Chapter 5 - Troubleshooting
The Lambdatronic controls the connected heating components. All parts of
the boiler are deactivated.
Industriestraße 12
A-4710 Grieskirchen
info@froeling.com
www.froeling.com
2
Page 11
B 037 05 08_en
Need help?
Do you have a question about the Lambdatronic P 3200 and is the answer not in the manual?