Asset Registration; End-To-End Data Check; Plant Viewer Access For End Users - ABB VSN700 Product Manual

Abb vsn700 data logger product manual
Table of Contents

Advertisement

2. The data logger acts as a router. From your laptop connected to Eth1, verify internet
connectivity by opening up an Internet browser window and connecting to
www.auroravision.net.
3. The remaining steps for commissioning are performed via the Internet to check end-to-end
communications. Proceed with one of the following steps:

Asset registration

Asset registration is performed via the Administration tool in Aurora Vision. Asset registration
assigns the MAC address of your logger to a specific plant in Aurora Vision. Asset Registration can
be performed before or after the on-site installation is complete. When you register the data logger,
all the assets (inverters and other devices) reporting to the data logger are also registered. A Plant
must be created on Aurora Vision using the Administration tool before the data logger can be
assigned and registered to it. Note that access to Administration tool requires an Aurora Vision
User ID and password with Administrator privileges.
From the data logger's user interface, click the Logger Registration button to go to the Asset
Registration on the Administration page of Portfolio Plant Manager. If you are not using the data
logger's web-based user interface, go to https://admin.auroravision.net/customeradmin. Select
Administration > Register Logger and type in the MAC address of the data logger. Follow the
steps on the Asset Registration page to select the plant that the data logger will be associated with.
See the Plant Portfolio Manager Users Guide for help in using the Administration tool for asset
registration. Go to

End-to-end data check

The last check is to make sure that data is actually being reported and is visible on the Aurora
Vision portal. Wait 15 minutes and log on to
Internet connected device. Within Aurora Vision, go to the Plant > Dashboard page for the plant
and open the Device Status panel. Verify that the energy readings agree with the inverter(s) and
that all of the monitored devices are communicating, as indicated by the Last Reported time.

Plant Viewer access for end users

The installer must supply the user with their unique Plant Viewer URL so they can monitor their
system. To find the URL for a specific user's plant within Aurora Vision, follow these steps:
1. Log on to Plant Portfolio Manager at
If you are not responsible for these remaining steps, be sure to pass on the MAC address
(Logger ID) information to the responsible party. Remove the cable from Eth1. Installation
is complete.
If asset registration is already complete, proceed to the section on End-to-End Data
Check.
If asset registration is not complete, proceed to the next section on Asset Registration.
https://docs.auroravision.net
VSN700 Data Logger Product Manual
for all the latest product documentation.
www.auroravision.net
www.auroravision.net
and go to Plant > Management.
- 15 -
using a web browser on an

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Vsn700-01 seriesVsn700-03 seriesVsn700-05 series

Table of Contents