DISASSEMBLY PROCEDURE

15. How to detach and attach the quick joint

Refer to the following steps when detaching and attaching the
quick connection.
(1) Remove the clip. (Photos 15-1 and 15-2)
(2) Separate the connected parts to remove the O-ring. (Photo
15-3)
• Do not reuse the removed O-ring.
• Wipe off if dirt or foreign matters are found on the sealing
surface where the O-ring touches.
(3) Apply grease on the O-ring using a plastic bag, etc. (Photo
15-4)
(4) Attach the O-ring to the male part of quick connection. (Pho-
to 15-5)
• Keep the O-ring free from dirt or foreign matters.
(5) Connect the male and female parts of the quick connection.
(Photo 15-6)
(6) Attach the clip. (Photo 15-7)
• Ensure to attach the wider diameter of the clip to the fe-
male side. Failure to do so, it may cause water leak at the
connected part. (Photo 15-8)
Photo 15-3
Female
Male
Photo 15-6
OCH571
Photo 15-4
O-ring
Photo 15-7
77
PHOTOS & ILLUSTRATION
Photo 15-1
Photo 15-2
Clip
Photo 15-5
Plastic
bag
O-ring
Photo 15-8
Clip
Clip
Gap