Compact A High efficiency combi boiler Users Instructions Installation & Servicing Instructions THESE INSTRUCTIONS TO BE RETAINED BY USER Vokèra is a licensed member of the Benchmark scheme which aims to improve the standards of installation and commissioning of domestic hot water systems in the UK.
Users instructions Things you should know Page Installation Page Gas appliances Delivery Electrical supply Contents Guarantee registration card Unpacking Appliance Log Book (UK only) Preparation for mounting the appliance How does it work? Fitting the flue Dimensions Connecting the gas & water Clearances required Electrical connections Frost protection system...
USERS INSTRUCTIONS INTRODUCTION Dear Customer Your Vokèra Compact boiler has been designed to meet and exceed the very latest standards in gas central heating technology, and if cared for, will give years of reliable use and efficiency. Please therefore take some time to read these instructions carefully. Do’s and Don’t’s - Do ensure that the system pressure is periodically checked - Do ensure that you know how to isolate the appliance in an emergency...
Page 4
Fig. 1 YELLOW LED TEMPERATURE RED LED SELECTOR HYDROMETRE GREEN LED MODE SELECTOR SWITCH HEATING TEMPERATURE SELECTOR BOILER STATUS LED Green LED Boiler is working/responding to a heating/hot water request Red LED Boiler has identified a fault and has failed-safe. Refer to instructions on how to reset Yellow LED Service operation DHW TEMPERATURE SELECTOR Move the selector clockwise to increase the hot water outlet temperature, or counter-clockwise to reduce the temperature...
2. GETTING STARTED 2.3 LIGHTING THE BOILER 2.1 BEFORE SWITCHING ON Ensure the gas and electrical supply to the boiler are turned on. Before switching the appliance on, please familiarise yourself with: Turn the mode selector switch to the ON position. When there - how to isolate the appliance from the gas, water, and elec- is a request for heating or hot water via the time clock or tricity supplies;...
APPLIANCE STATUS LED AND FAULT CODES Alarm type Led RED Led YELLOW Led GREEN Action Purge cycle mode active BLINKING BLINKING BLINKING Alarm high limit thermostat Final BLINKING Reset appliance. Call engineer if fault re-occurs Alarm system water pressure Final Check/refill system pressure, reset, check.
INSTALLATION AND SERVICING INSTRUCTIONS INTRODUCTION also be used with the Vokèra twin flue system. The Compact comprises a range of high-efficiency The Compact is approved for use with C13 & C33 type flue combination boilers with outputs to DHW of 25kW and 30kW applications.
SECTION 1 - DESIGN PRINCIPLES AND OPERATING SEQUENCE 1.5 SAFETY DEVICES 1.1 PRINCIPLE COMPONENTS • A fully integrated electronic control board featuring electronic When the appliance is in use, safe operation is ensured by: • a water pressure switch that monitors system water pressure temperature control, anti-cycle control, pump over-run, self- and will de-activate the pump, fan, and burner should the diagnostic fault indicator, full air/gas modulation...
SECTION 2 - TECHNICAL DATA 2.1 Central Heating Compact 25 Compact 29 Heat input (kW) 20.00 Maximum heat output (kW) 60/80°C 19.50 24.40 Minimum working pressure 0.5 bar Maximum working pressure 2.7 bar Minimum flow rate 350 l/h 2.2 Domestic Hot Water Compact 25 Compact 29 Heat input (kW)
Below an opening or window on a pitched roof 2000 mm From a vertical terminal to an adjacent opening (window, air-brick, etc.) (call Vokera technical for advice) From a vertical terminal to an adjacent vertical terminal 300 mm (only if both terminals are the same hight)
SECTION 3 - GENERAL REQUIREMENTS (UK) This appliance must be installed by a competent person in people have access (including balconies or flat roofs) the accordance with the Gas Safety (Installation & Use) terminal must be protected by a guard of durable material. Regulations.
with an approved non-return valve and stopcock for isolation 3.11 SHOWERS purposes. The feed pipe should be connected to the return If the appliance is intended for use with a shower, the shower pipe as close to the boiler as possible. must be thermostatically controlled and be suitable for use 3.6.8 FREQUENT FILLING with a combination boiler.
3A.7 ELECTRICAL SUPPLY terminal must be protected by a guard of durable material. The guard must be fitted centrally over the terminal. Refer to I.S. 813, The appliance is supplied for operation on 230V @ 50Hz when the terminal is 0.5 metres (or less) below plastic guttering electrical supply;...
SECTION 4 - INSTALLATION 29450126 1000mm extension 1000mm 4.1 DELIVERY 29450127 2000m extension 2000mm Due to the weight of the appliance it may be necessary for two 29450128 Telescopic extension 350/730mm people to lift and attach the appliance to its mounting. The Wall bracket pack (5) 208mm appliance is contained within a heavy-duty cardboard carton.
Page 15
4.5.2 CONCENTRIC VERTICAL FLUE The appliance can be used with either the Vokèra condensing 60/100mm concentric flue system or the optional 80/125mm concentric flue system. NOTE These instructions relate only to the Vokèra condensing 60/ 100mm concentric flue system. For specific details on the installation of the 80/125mm concentric flue system please refer to the instructions supplied.
Page 16
IMPORTANT Once the bracket has been secured to the wall, mount the The vertical flue terminal is 1.0 metre in length and cannot be appliance onto the bracket. cut; therefore it may be necessary to adjust the height of the appliance to suit or use a suitable extension.
pushed 50mm onto the male spigots of the concentric to twin converter. NOTE Seal the flue terminal assembly to the wall using cement or a suitable alternative that will provide satisfactory weatherproofing. The interior and exterior trim can now be fitted.
• store the casing and screws safely until required. Re-fit in the reverse order Hot water • gently lower the control fascia until it rests. outlet 4.7.2 APPLIANCE TERMINAL BLOCK The appliance terminal block is located on the rear of the cock Cold water inlet control fascia.
SECTION 5 - COMMISSIONING (see 7.8) particularly continuity, polarity and resistance to 5.1 GAS SUPPLY INSTALLATION earth; Inspect the entire installation including the gas meter, test for • ensure the 3 AMP fuse – supplied with the appliance – has tightness and purge.
5.12 FINAL CHECKS us using the envelope supplied • ENSURE ALL TEST NIPPLES ON THE APPLIANCE GAS • online at: vokera.co.uk VALVE ARE TIGHT AND CHECKED FOR TIGHTNESS. • for UK residents by calling: 0870 607 0281 • ENSURE THE APPLIANCE FLUE SYSTEM IS FITTED •...
6.5 PUMP ASSEMBLY (fig. 21) Carry out component removal procedure as described in 6.4. Disconnect and remove the pump outlet pipe (A) from the pump assembly/combustion chamber connection. Remove the expansion pipe locking pin (B) from the top of the pump assembly and withdraw the flexible pipe.
6.12 GAS VALVE (fig. 26) Carry out component removal procedure as described in 6.4. The gas valve must be changed as complete unit. Disconnect the electrical plug and leads from the gas valve, slacken and unscrew gas valve inlet and outlet connections. Please note, the sealing washers (Q) must be discarded and replaced with new sealing washers.
6.16 MAIN HEAT EXCHANGER (fig. 29) Carry out component removal procedure as described in 6.4. Remove the air chamber front cover. Locate and remove the gas pipe locking pin (A1) and swing/rotate the gas pipe away from the fan assembly (B1), (if necessary unscrew the gas pipe from the gas valve G1).
6.20 FLUE COLLECTOR REMOVAL (fig. 33) Carry out component removal procedure as described in 6.4. Remove the air chamber front cover. Remove the heat exchanger as per 6.16. Locate and remove the screw (Y1) that secures the flue gas analysis test point cover (Z1). Disconnect the flues thermistor wiring connections.
SECTION 7 - CHECKS, ADJUSTMENTS AND FAULT FINDING burner will switch off. The built-in anti-cycle device prevents 7.1 CHECKING APPLIANCE OPERATION the burner from re-lighting for approximately 3-minutes. When carrying out any repairs or servicing to the appliance, the When the temperature of the flow sensor falls below the relevant commissioning procedure must be undertaken to set point (- hysterisis), the burner will re-light.
7.3.1 CO FUNCTION SETTINGS Locate the CO button (see 7.3) Select the main selector switch in position FUNCTIONS ACTION ON THE BUTTON LED STATUS combustion analysis mode press once = burner running at maximum heating yellow led blinking gas valve maximun setting press twice = burner running at maximum DHW yellow led blinking + red led fixed gas valve minimum setting...
NOTE COMPONENT VALUES & Should it be found that the fuse has failed but no fault is CHARACTERISTICS indicated, a detailed continuity check will be required to trace the fault. A visual inspection of components may also assist in COMPONENT VALUE locating the fault.
SECTION 8 - WIRING DIAGRAMS 8.1 EXTERNAL WIRING MECHANICAL CLOCK - The appliance comes with a factory fitted (TA) link to allow RADIO FREQUENCY RECEIVER basic operation of the boiler via the mode selector switch. If external controls are to be added to the system, they must be connected to the appliance as shown in the following dia- grams.
SECTION 10 - LPG INSTRUCTIONS 10.1 RELATED DOCUMENTS BS 5440 PARTS 1 & 2 FLUES & VENTILATION REQUIREMENTS BS 5449 PART 1 FORCED CIRCULATION OF HOT WATER SYSTEMS BS 5482 PART 1 DOMESTIC BUTANE & PROPANE GAS BURNERS IN PERMAMENT DWELLINGS BS 5546 INSTALLATION OF GAS HOT WATER SUPPLIES FOR DOMESTIC...
Page 36
10.6.2 GAS VALVE MAXIMUM SETTING Set the CO button at maximum (see 10.3.1), once the maximum is obtained check that it corresponds with the appropriate CO value (Maximum) for the respective appliance. If the CO reading is correct, proceed to gas valve minimum setting (10.7.2).
Page 40
Registered address: Vokèra Ltd Borderlake House Unit 7 Riverside Industrial Estate London Colney Herts AL2 1HG enquiries@vokera.co.uk www.vokera.co.uk www.vokera.ie Sales, General Enquires T 0844 391 0999 F 0844 391 0998 Vokèra Ireland West Court, Callan Co Kilkenny T 056 7755057 F 056 7755060 Vokèra Limited reserve the right to change...