Introduction Congratulations on your purchase of a Heatrae Sadia Megafl o High Effi ciency un- vented water heater. The Megafl o is manufactured in the UK from top quality materials and meets all the latest relevant safety and constructional standards. The high grade Duplex stainless steel cylinder offers exceptional strength and corrosion resistance which is backed by a 25 year guarantee.
AND EXPERIENCE, UNLESS THEY HAVE BEEN GIVEN SUPERVISION OR INSTRUCTION CONCERNING THE USE OF THE APPLIANCE BY A PERSON RESPONSIBLE FOR THEIR SAFETY. THE MEGAFLO MUST BE INSTALLED (SECTIONS 2 - 5), COMMISSIONED (SECTION 6) AND MAINTAINED (SECTIONS 8 - 10) BY A COMPETENT INSTALLER IN ACCORDANCE...
Page 5
the system (Note: indirect controls housing hinges open to the left hand side). Please do not install valves or pipework (except discharge pipe) within 50mm (2”) of the T&P relief valve to allow your insulation set to be fi tted. The insulation set is important to ensure heat and energy conservation.
Page 6
2.5 LIMITATIONS 2.5 LIMITATIONS The Megafl o unvented water heater should not be used in any of the following instances: • Solid fuel boilers or any other boiler in which the energy input is not under effective ther mostatic control unless additional and appropriate safety measures are installed. •...
Installation - General 3.1 PIPE FITTINGS 3.1 PIPE FITTINGS All pipe connections to the Megafl o are made via 22mm compression fi ttings directly to the unit (nuts and olives supplied). The fi ttings are also threaded 3/4” BSP male parallel should threaded pipe connections be required.
Page 8
of fl ow arrows). The cold water balanced draw off connection should be taken from between the Cold Water Combination Valve and the Expansion Core Unit (see Figure 5). The Expan- sion Valve connection on the Cold Water Combination Valve should remain blanked off using the blanking nut and seal provided.
Page 11
Under no circumstances should the factory fi tted Temperature/Pressure Relief Valve Under no circumstances should the factory fi tted Temperature/Pressure Relief Valve be removed other than by Authorised Heatrae Sadia personnel. To do so will invali- be removed other than by Authorised Heatrae Sadia personnel. To do so will invali- date any guarantee or claim.
Page 12
ii) The Cold Water Combination Valve must be fi tted to the mains water supply to the Megafl o unit. ii) The Cold Water Combination Valve must be fi tted to the mains water supply to the Megafl o unit. iii) No control or safety valves should be tampered with.
Page 13
3.10 DISCHARGE PIPEWORK 3.10 DISCHARGE PIPEWORK It is a requirement of Building Regulations that any discharge from an unvented system is conveyed to where it is visible, but will not cause danger to persons in or about the building. The tundish and discharge pipes should be fi tted in accordance with the requirements and guidance notes of Building Regulations.
Page 14
d. have discharges visible at both the tundish and the fi nal point of discharge, but where this is not possible or is practically diffi cullt there should be clear visibilty at one or other of these locations. Examples of acceptable discharge arrangements are: i.
Page 15
Table 1 - Sizing of copper discharge pipe (D2) for common T&P relief valve sizes Table 1 - Sizing of copper discharge pipe (D2) for common T&P relief valve sizes Figure 8 - Schematic discharge pipe arrangement Figure 8 - Schematic discharge pipe arrangement...
DO NOT OPERATE THE IMMERSION HEATER(S) UNTIL THE MEGAFLO HAS BEEN DO NOT OPERATE THE IMMERSION HEATER(S) UNTIL THE MEGAFLO HAS BEEN FILLED WITH WATER.
Page 17
DISCONNECT FROM THE MAINS SUPPLY BEFORE REMOVING ANY COVERS NEVER ATTEMPT TO REPLACE AN IMMERSION HEATER OTHER THAN WITH THE REC- NEVER ATTEMPT TO REPLACE AN IMMERSION HEATER OTHER THAN WITH THE REC- OMMENDED HEATRAE SADIA MEGAFLO SPARE PART OMMENDED HEATRAE SADIA MEGAFLO SPARE PART Figure 9 -...
Installation - Indirect units 5.1 BOILER SELECTION 5.1 BOILER SELECTION The Megafl o Indirect (CL) models are suitable for use with most gas or oil fi red boilers compat- ible with unvented systems i.e. fi tted with a temperature control thermostat and thermal cut-out. If in doubt consult the boiler manufacturer.
Page 19
5.5 IMMERSION HEATER(S) 5.5 IMMERSION HEATER(S) The Megafl o indirect units (CL models) are supplied with an immersion heater which can be used as an alternative heat source should the boiler supply need to be isolated from the Megafl o unit. The immersion heater is located within the controls housing. Refer to Sec- tions 4.2 and 4.3 and Diagram 9 for details of wiring and operation of the immersion heater.
Page 20
Figure 12 - Indirect controls housing details Figure 12 - Indirect controls housing details INDIRECT THERMAL CUT-OUT RESET BUTTON INDIRECT THERMOSTAT THERMAL ADJUSTMENT CUT-OUT INDIRECT THERMOSTAT CABLE CLAMPS TERMINAL BLOCK NOTE: THE HOUSING COVER AND ELEMENT ASSEMBLY HAVE BEEN REMOVED FROM THIS VIEW FOR CLARITY...
Commissioning 6.1 FILLING AND FLUSHING THE MEGAFLO 6.1 FILLING AND FLUSHING THE MEGAFLO Ensure that all fi ttings and immersion heaters are correctly fi tted and tightened. An immer- sion heater key spanner is provided to aid in tightening the immersion heater(s).
Page 24
Switch on the boiler, ensure the programmer is set to Domestic Hot Water. Allow the Mega- fl o unit to heat up and check that the indirect thermostat and 2-port motorised valve operate correctly. A storage temperature of approx. 60 C is recommended (approx.
IF WATER ISSUES FROM THE TEMPERATURE/PRESSURE RELIEF VALVE ON THE IF WATER ISSUES FROM THE TEMPERATURE/PRESSURE RELIEF VALVE ON THE MEGAFLO UNIT REFER TO SECTION 7.4 FIRST. IF THIS DOES NOT RECTIFY THE MEGAFLO UNIT REFER TO SECTION 7.4 FIRST. IF THIS DOES NOT RECTIFY THE...
Page 26
The air volume will be automatically recharged as the unit refi lls. If after following the above actions water still discharges from the Expansion Relief Valve further advice should be sought from a competent installer or the Heatrae Sadia Service Department.
Maintenance should be carried out by a competent person and any replacement parts used should be authorised Heatrae Sadia Megafl o spare parts. It is recommended that maintenance is carried out every 12 months and includes the checks detailed in 8.2 and 8.3 below.
Page 28
8.5 DESCALING IMMERSION HEATER(S) 8.5 DESCALING IMMERSION HEATER(S) Open the cover(s) to the immersion heater housing(s) and disconnect wiring from immersion heater(s). Remove the thermostat by carefully pulling outwards from the immersion heater. Un- screw immersion heater backnut(s) and remove immersion heater from the unit. A key spanner is supplied with the Megafl...
Fault Finding & Servicing 9.1 IMPORTANT 9.1 IMPORTANT Servicing should only be carried by authorised Heatrae Sadia Service Engineers or Agents or by installers competent in the installation and maintenance of unvented water heating systems. Any spare parts used MUST be authorised Heatrae Sadia parts.
Page 30
Any work carried out on the Megafl o unvented water heater and its as- sociated controls MUST be carried out by a competent installer for unvented water heating systems. In case of doubt contact the Heatrae Sadia Service Department (see Section 12).
Any disinfection has been carried out in accordance with BS 6700. iii) It has not been modifi ed in any way other than by Heatrae Sadia Heating. It has only been used for the storage of wholesome water. It has not been installed in a location liable to be subjected to frost, nor has it been tampered with or been subjected to misuse or neglect.