INTRODUCTION Thank you for purchasing a Heatrae Multipoint Instantaneous. The unvented pressure system water heater is manufactured to the highest standards and has been designed to meet all the latest relevant safety specifications. Please read and understand these instructions before starting work.
1.0 IMPORTANT INSTALLATION POINTS 1.1 Products manufactured by Heatrae Sadia are to British and European Standards.These appliances are safe and without risk, provided they are installed, used and maintained in good working order in accordance with our instructions and recommendations. 1.2 Please read and understand these instructions before starting work and retain them for later use.
PLUMBING 1.12 T he plumbing installation must comply with Water Regulations. 1.13 The supply pipe must be flushed to clear debris. 1.14 DO NOT solder pipes or fittings within 300mm of the heater once the pipe work is located in the appliance, as heat transfer can damage components. 1.15 A ll plumbing connections must be completed and checked for leaks before making the electrical connections. ELECTRICAL 1.16 B efore fitting the appliance, ensure that the consumer unit and any switches are suitable for the additional load. If in doubt, contact your electricity supplier or a qualified electrician.
REQUIREMENTS ELECTRICAL REQUIREMENTS 3.1 This appliance must be earthed. 3.2 The installation, supply cable and circuit protection must conform to the latest BS7671 ‘Requirements for electrical installations’ (IEE Wiring Regulations). 3.3 The Multipoint Instantaneous heater must only be connected to a 230/240V ac supply. 3.4 Before making any electrical connections within the installation, make sure that no terminal is live. If in doubt, SWITCH OFF the whole installation at the consumer unit or switch fuse (where fitted). 3.5 The Multipoint Instantaneous heater must be connected to its own independent electrical circuit.
Page 8
IEE regulations Make cut-out using sharp knife RCD (can be part of the consumer unit) Multipoint Instantaneous unit (use rear entry when it is possible) Figure 5 - Rear cable entry 80A or 100A main switch Meter Meter ‘tails’...
PLUMBING 4.6 Decide where to connect to the water mains for your feed to the Multipoint Instantaneous. Ensure that the pipe you have selected is not a gas pipe, a hot water pipe, or from a cold water storage tank. 4.7 Cut the necessary pipe work to length, offer up to the installation before making any soldered joints.
Page 10
4.15 Connect all other components as per Figure 3. 4.16 T urn the isolating stop valve on slowly and check for leaks in all pipe work, rectify as necessary. 4.17 T urn off the isolating stop valve. 4.18 Place the cover onto the back plate. 4.19 Secure the cover to back plate using screw provided. 5.0 COMMISSIONING 5.1 Once installed, the heater will operate automatically when the outlet valve is opened. The valve must be opened fully to obtain the set flow/temperature. Reduced flow at the outlet will result in hotter water being delivered. 5.2 On closing the outlet valve the heating element will automatically shut down provided this tap has been fully turned off by the user. SETTING FLOW RATE 5.3 To set the flow rate, make sure the water and power are turned off. Open the outlet valve fully (see figure 3) and close the flow...
6.0 MULTIPLE INSTALLATION 6.1 When larger volumes of water are required than can be provided by one heater, multiple installations can be made by connecting a number of heaters in PARALLEL of the cold feed manifold (See Figure 6). This is the ONLY method that is recommended provided all heaters receive acceptable flow rates (2.5ltr/min recommended). DO NOT plumb these heaters in series. 6.2 To set the heaters in this arrangement use the appropriate procedure as described previously. Each heater in parallel must be set individually. 6.3 In this application restrictors capable of closing flow completely should be used so that as each heater is set in turn, the other heaters in the installation may be isolated.
"split load" consumer (earth leakage unit on initial installation, check that the circuit breaker) neutral core of the Multipoint Instantaneous feed cable has operated is connected to the "protected" neutral bar of the unit 5. Water emerges A.
8.0 SPARE PARTS The following comprehensive list of spare parts is available for your Multipoint instantaneous water heater. Please refer to the rating label on the right hand side of your heater before ordering to ensure the correct spare parts are obtained.
4. The unit has been used only for heating potable water. The unit is not guaranteed against damage by frost or due to the build up of scale. Please note that if Heatrae Sadia personnel or agents are requested to de scale a unit, this work will be chargeable. This guarantee does not affect the statutory rights of the consumer.