Jump Frequency - Avoiding Resonant Frequencies - Toshiba TOSVERT VF-MB1 Instruction Manual

Industrial inverter for 3-phase induction motors
Hide thumbs Also See for TOSVERT VF-MB1:
Table of Contents

Advertisement

6.11 Jump frequency - avoiding resonant frequencies

f270 : Jump frequency 1
f271 : Jumping width 1
f272 : Jump frequency 2
f273 : Jumping width 2
f274 : Jump frequency 3
f275 : Jumping width 3
 Function
Resonance due to the natural frequency of the mechanical system can be avoided by jumping the
resonant frequency during operation. During jumping, hysteresis characteristics with respect to the jump
frequency are given to the motor.
Output command frequency
[Parameter setting]
Title
Jump frequency 1
f270
Jumping width 1
f271
Jump frequency 2
f272
f273
Jumping width 2
Jump frequency 3
f274
Jumping width 3
f275
Note 1: Do not set the jump parameters, if multiple jump frequency setting width overlap.
Note 2: During acceleration or deceleration, the jumping function is disabled for the operation frequency.
(Hz)
Jump frequency 3 ()
Jump frequency 2 ()
Jump frequency 1 ()
0
Frequency setting signal
Function
F-29
Jumping width 3 ()
Jumping width 2 ()
Jumping width 1 ()
Adjustment range
0.0- fh (Hz)
0.0-30.0 (Hz)
0.0- fh (Hz)
0.0-30.0 (Hz)
0.0- fh (Hz)
0.0-30.0 (Hz)
E6581697
6
Default setting
0.0
0.0
0.0
0.0
0.0
0.0

Hide quick links: