Motor Thermal Protection - Toshiba TOSVERT VF-MB1 Instruction Manual

Industrial inverter for 3-phase induction motors
Hide thumbs Also See for TOSVERT VF-MB1:
Table of Contents

Advertisement

Branch circuit protection must be provided in accordance with the Canadian Electrical Code and any additional
local codes.
9.2.3
Compliance with Peripheral devices
Use the UL listed fuses at connecting to power supply.
Short circuit test is performed under the condition of the power supply short-circuit currents in below.
These interrupting capacities and fuse rating currents depend on the applicable motor capacities.
 AIC, Fuse and Wire sizes
Voltage
Inverter model
(V)
Markig
Y
VFMB1S-2002PL
240
VFMB1S-2004PL
240
VFMB1S-2007PL
240
VFMB1S-2015PL
240
VFMB1S-2022PL
240
VFMB1-4004PL
500
VFMB1-4007PL
500
VFMB1-4015PL
500
VFMB1-4022PL
500
VFMB1-4037PL
500
VFMB1-4055PL
500
VFMB1-4075PL
500
VFMB1-4110PL
500
VFMB1-4150PL
500
Suitable for use on a circuit capable of delivering not more than___X___rms symmetrical kilo Amperes,___Y___Volts
maximum, when protected by___Z1___with a maximum rating of___Z2___.
(1) Input withstand rating is that for which the product has been designed thermally. Installation on a supply greater than
this level will require additional inductance to satisfy this level.
(2) Output interrupt rating relies on Integral solid state short circuit protection. This does not provide branch circuit
protection. Branch circuit protection must be provided in accordance with the National Electrical Code and any
additional local codes. This is dependant on the type of installation.
9.2.4

Motor thermal protection

Selects the electronic thermal protection characteristics that fit with the ratings and characteristics of the motor.
(Refer to section 3.5)
In case of multi motor operation with one inverter, thermal relay should be connected to each motor.
Input
Output
withstand
Interrupt
rating (kA)
rating (kA)
(1)
X (2)
1
5
1
5
1
5
1
5
1
5
5
5
5
5
5
5
5
5
5
5
22
22
22
22
22
22
22
22
I-7
Branch circuit
Rating
Cable sizes of
protection
(A)
Z1
Z2
Class CC
7
Class J
15
Class J
25
Class J
40
Class J
45
Class CC
6
Class CC
6
Class CC
12
Class J
15
Class J
25
Class J
40
Class J
40
Class J
60
Class J
70
E6581697
Earth Cable
power circuit
-
-
AWG 14
AWG 14
AWG 14
AWG 14
AWG 14
AWG 14
AWG 10
AWG 12
AWG 10
AWG 10
AWG 14
AWG 14
AWG 14
AWG 14
AWG 14
AWG 14
AWG 14
AWG 14
AWG 12
AWG 14
AWG 10
AWG 10
AWG 8
AWG 10
AWG 8
AWG 10
AWG 6
AWG 10