Diagnostic Alarms - Eurotherm 2208e Installation And Operation Handbook

Hide thumbs Also See for 2208e:
Table of Contents

Advertisement

Operation

1.12.3 DIAGNOSTIC ALARMS

These indicate that a fault exists in either the controller or the connected devices.
Display
What it means
shows
EE.Er
Electrically Erasable
Memory Error:
The value of an operator
or configuration
parameter has been
corrupted
S.br
Sensor Break:
Input sensor is
unreliable or the input
signal is out of range
L.br
Loop Break:
The feedback loop is
open circuit
Ld.F
Load failure
Indication that there is a
fault in the heating
circuit or the solid state
relay
SSr.F
Solid state relay failure
Indication that there is a
fault in the solid state
relay
Htr.F
Heater failure
Indication that there is a
fault in heating circuit
HW.Er
Hardware error
Indication that a module
is the wrong type
no. io
No I/O module
Modules are configured
but not fitted
Figure 1.20a Diagnostic alarms - continued on the next page
1-26
Installation and Operation Handbook
What to do about it
This fault will automatically take you into
configuration level. Check all of the configuration
parameters before returning to operator level. Once
in operator level, check all of the operator
parameters before resuming normal operation. If
the fault persists or occurs frequently, contact your
supplier
Check that the sensor is correctly connected
Check that the heating and cooling circuits are
working properly
This is an alarm generated by feedback from a
TE10S solid state relay (SSR) operating in PDS
SSRx mode. It indicates either an open or short
circuit SSR, blown fuse, missing supply or open
circuit heater
This is an alarm generated by feedback from a
TE10S solid state relay (SSR) operating in PDS
SSRx mode. It indicates either an open or short
circuit condition in the SSR
This is an alarm generated by feedback from a
TE10S solid state relay (SSR) operating in PDS
SSRx mode. It indicates either a blown fuse,
missing supply or open circuit heater
Check that the correct modules are fitted
This error message normally occurs when pre-
configuring a controller without installing any of the
required I/O modules
2208e and 2204e Controller

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the 2208e and is the answer not in the manual?

Questions and answers

George
April 15, 2025

how do I get the output 2 to come on? Recently had to swap out the card, I believe I got all the parameters switched over but the output 2 is not kicking on and I'm getting 3FSH fault. Any advice will be greatly appreciated

1 comments:
Mr. Anderson
April 15, 2025

To enable output 2 on a Eurotherm 2208e after swapping out the card and resolving a 3FSH fault, follow these steps:

1. Ensure the correct I/O module for output 2 is physically installed.
2. Power cycle the controller if not already done.
3. Enter configuration mode on the controller.
4. Navigate to the I/O module setup section.
5. Configure output 2 settings as required (e.g., type, function).
6. Exit configuration mode and save settings.

The output should now be enabled and functional.