AY-ZP35PR
Function
10 AC overcurrent
Indoor and outdoor units stop
error in compres-
if outdoor AC current exceeds
sor OFF status
about 3 A while compressor is in
non-operation status.
11 AC maximum cur-
Compressor stops if coutdoor
rent error
AC current exceeds 17 A.
12 AC current defi-
Compressor stops if operating
ciency error
frequency is 50 Hz or higher and
outdoor AC current is about 2.0
A or lower.
13 T h e r m i s t o r i n -
Compressor stops if high and
stallation error or
low values of temperatures
4-way valve error
detected by outdoor unit heat
exchanger thermistor (TH2) and
2-way valve thermistor (TH5) do
not match operating cycle.
14 Compressor high
Compressor stops if compressor
temperature error
chamber thermistor (TH1) ex-
ceeds about 114°C, or if there is
short-circuit in TH1.
15 Outdoor unit heat
Compressor stops if there is
exchanger ther-
short-circuit in outdoor unit heat
mistor short-cir-
exchanger thermistor (TH2).
cuit error
16 Outdoor unit out-
Compressor stops if there is
side air temper-
short-circuit in outdoor unit out-
ature thermistor
side air temperature thermistor
short-circuit error
(TH3).
17 Outdoor unit suc-
Compressor stops if there is
t i o n t h e r m i s t o r
short-circuit in outdoor unit suc-
short-circuit error
tion thermistor (TH4).
18 O u t d o o r u n i t
Compressor stops if there is
2-way valve ther-
short-circuit in outdoor unit 2-way
mistor short-cir-
valve thermistor (TH5).
cuit error
19 Outdoor unit heat
Compressor stops if there is
exchanger ther-
open-circuit in outdoor unit heat
mistor open-cir-
exchanger thermistor (TH2).
cuit error
20 Outdoor unit out-
Compressor stops if there is
side air temper-
open-circuit in outdoor unit out-
ature thermistor
side air temperature thermistor
open-circuit error
(TH3).
21 Outdoor unit suc-
Compressor stops if there is
t i o n t h e r m i s t o r
open-circuit in outdoor unit suc-
open-circuit error
tion ther-mistor (TH4).
22 O u t d o o r u n i t
Compressor stops if there is
2-way valve ther-
open-circuit in outdoor unit 2-way
mistor open-cir-
valve thermistor (TH5).
cuit error
23 Outdoor unit dis-
Compressor stops if there is
charge thermistor
open-circuit in outdoor unit dis-
open-circuit error
charge thermistor (TH1).
24 Serial signal error Compressor stops if outdoor unit
cannot receive serial signal from
indoor unit for 30 seconds.
25 Compressor start-
Compressor stops if compressor
up error
fails to start up.
26 Compressor rota-
Compressor stops if there is no
tion error (at 120°
input of position detection signal
energizing)
from compressor or input is ab-
normal.
27 Outdoor unit DC
Operation stops if there is no in-
fan error
put of rotation pulse signal from
outdoor unit fan motor for 30
seconds.
28 PAM overvoltage
Compressor stops if DC voltage
error
is 400 V or higher.
Description
Detection period
When compressor is in
non-operation
When compressor is in
operation
When compressor is in
operation
3 minutes after com-
pressor startup
When in operation
At compressor startup
At compressor startup
At compressor startup
At compressor startup
At compressor startup
At compressor startup
At compressor startup
At compressor startup
At compressor startup
When in operation
At compressor startup
Compressor operating
at 120° energizing
When outdoor unit fan is
in operation
When in operation
Operation
Reset condition
Replacement of defec-
tive parts such as IPM
Operation OFF or ON
Operation OFF or ON
Operation OFF or ON
Operation OFF or ON
Operation OFF or ON
Operation OFF or ON
Operation OFF or ON
Operation OFF or ON
Operation OFF or ON
Operation OFF or ON
Operation OFF or ON
Operation OFF or ON
Operation OFF or ON
Reset after reception of
serial signal
Operation OFF or ON
Operation OFF or ON
Operation OFF or ON
Operation OFF or ON
3-2
Self-diagnosis result
display
Indoor
Indoor unit
unit error
display
Yes
1
Yes
Yes
Yes
2
Yes
Yes
Yes
2
Yes
Yes
Yes
2
Yes
Yes
Yes
2
Yes
Yes
Yes
2
Yes
Yes
Yes
2
Yes
Yes
Yes
2
Yes
Yes
Yes
2
Yes
Yes
Yes
2
Yes
Yes
Yes
2
Yes
Yes
Yes
2
Yes
Yes
Yes
2
Yes
Yes
Yes
2
Yes
Yes
None
None
None
Yes
3
Yes
Yes
Yes
3
Yes
Yes
Yes
2
Yes
Yes
Yes
2
Yes
Yes
Outdoor
unit