Mitsubishi Electric FR-F720-00046 Instruction Manual page 203

F700 series
Hide thumbs Also See for FR-F720-00046:
Table of Contents

Advertisement

Selection of operation mode and
operation location
(6) Switching of command source by external terminal (X67)
⋅ In Network operation mode, the command source switching signal (X67) can be used to switch the start command
source and speed command source. This signal can be utilized to control the signal input from both the control
terminal and communication.
⋅ Set "67" in any of Pr. 178 to Pr. 189 (input terminal function selection) to assign the X67 signal to the control terminal.
⋅ When the X67 signal is off, the start command source and speed command source are control terminal.
X67 Signal State
No signal assignment
ON
OFF
REMARKS
⋅ The ON/OFF state of the X67 signal is reflected only during a stop. It is reflected after a stop when the terminal is switched while
the inverter is running.
⋅ When the X67 signal is off, a reset via communication is disabled.
CAUTION
⋅ Changing the terminal assignment using Pr. 178 to Pr. 189 (input terminal function selection) may affect the other functions. Please
make setting after confirming the function of each terminal.
♦ Parameters referred to ♦
Pr. 28 Multi-speed input compensation selection
Pr. 59 Remote function selection
Pr. 79 Operation mode selection
194
Start Command Source
According to Pr. 338
Command is valid only from control terminal signal.
Refer to page 92.
Refer to page 93.
Refer to page 181.
Speed Command Source
According to Pr. 339

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents