Types of Monitor
Increments
Converter output
0.1V
voltage
Regenerative
0.1%
brake duty
Electronic thermal
relay function load
0.1%
factor
Output current
0.01A/0.1A
peak value
*5
Converter output
0.1V
voltage peak value
0.01kW/
Input power
0.1kW
0.01kW/
Output power
0.1kW
Load meter
0.1%
Cumulative
1h
energization time
*2
Reference voltage
output
Actual operation
1h
time
*2*3
Motor load factor
0.1%
Cumulative power
0.01kWh/
0.1kWh
*6
*4, *5
Power saving
effect
Variable
according
to
Cumulative saving
parameters
power
*6
PID set point
0.1%
PID measured
0.1%
value
PID deviation
0.1%
Input terminal
status
Output terminal
status
Option input
terminal status
Option output
terminal status
Pr. 52 Parameter
Pr. 54 (CA)
Setting Value
Pr. 158 (AM)
Parameter
PU main
Setting
DU LED
monitor
Value
8
*1
9
*1
10
*1
11
*1
12
*1
13
*1
*5
14
*1
*5
17
20
23
24
25
50
51
52
53
54
*1
55
*1
56
57
Monitor display and monitor output signal
Full-scale
value of the
terminal CA
and AM
400V class:
8
Displays the DC bus voltage value
800V
Brake duty set in Pr. 30 and Pr. 70 (Setting
9
Pr. 70
can be made for the 01800 or more)
Displays the motor thermal cumulative
10
100%
value on the assumption that the thermal
operation level is 100%.
Retains the peak value of the output
11
Pr. 56
current monitor and displays (clears at
every start)
Retains the peak value of the DC bus
400V class:
12
voltage value and displays (clears at every
800V
start)
Rated inverter
13
Displays power of the inverter input side
power
2
Rated inverter
14
Displays power of the inverter output side
power
2
Displays the torque current in % on the
17
100%
assumption that the Pr. 56 setting is 100%
Displays the cumulative energization time
since the inverter shipment
You can check the numbers of the monitor
value exceeded 65535h with Pr. 563.
Terminal CA: 20mA is output
21
Terminal AM: 10V is output
Displays the cumulative inverter running
time.
You can check the numbers of the monitor
value exceeded 65535h with Pr. 564.
Use Pr. 171 to clear the value.
(Refer to page 130 .)
Displays the output current value in % on
the assumption that the rated inverter
current value is 100%.
24
200%
Monitor value = output current monitor
value/rated inverter current
Displays the cumulative power amount
according to the output power monitor
Use Pr. 170 to clear the value.
(Refer to page 130.)
Inverter
Displays energy saving effect monitor
50
capacity
You can change the monitor to power
saving, power saving average value,
charge display and % display using
parameters.
(For details, refer to page 149.)
100%/
52
C42 or C44
Displays the set point, measured value and
100%/
deviation during PID control
53
C42 or C44
(For details, refer to page 226.)
Displays ON/OFF status of the input
terminal on the PU
(Refer to page 129 for DU display)
Displays ON/OFF status of the output
terminal on the PU
(Refer to page 129 for DU display)
Displays ON/OFF status of the input
terminal of the digital input option (FR-
A7AX) on the DU (refer to page 129 for
details)
Displays ON/OFF status of the output
terminal of the digital output option (FR-
A7AY) and relay output option (FR-A7AR)
on the DU (refer to page 129 for details)
Description
100 [%]
127
4

Hide quick links: