Mitsubishi Electric FR-F740-00023 Instruction Manual page 126

F700 series
Hide thumbs Also See for FR-F740-00023:
Table of Contents

Advertisement

Setting
Signal
Positive
Negative
Name
Logic
Logic
14
114
FDN
PID lower limit
15
115
FUP
PID upper limit
PID forward/reverse
16
116
RL
rotation output
17
MC1
Electric bypass MC1
18
MC2
Electric bypass MC2
19
MC3
Electric bypass MC3
25
125
FAN
Fan fault output
Heatsink overheat
26
126
FIN
pre-alarm
During inverter
45
145
RUN3
running and start
command is on
During deceleration at
46
146
Y46
occurrence of power
failure
During PID control
47
147
PID
activated
48
148
Y48
PID deviation limit
64
164
Y64
During retry
PID output
70
170
SLEEP
interruption
Commercial-power
71
RO1
supply side motor 1
connection RO1
Commercial-power
72
RO2
supply side motor 2
connection RO2
Commercial-power
73
RO3
supply side motor 3
connection RO3
Commercial-power
74
RO4
supply side motor 4
connection RO4
Inverter side motor 1
75
RIO1
connection RIO1
Inverter side motor 2
76
RIO2
connection RIO2
Inverter side motor 3
77
RIO3
connection RIO3
Inverter side motor 4
78
RIO4
connection RIO4
Pulse train output of
79
179
Y79
output power
85
185
Y85
DC feeding
90
190
Y90
Life alarm
Fault output 3
91
191
Y91
(power-off signal)
Function
Output when the feedback value falls below
the lower limit of PID control.
Output when the feedback value rises above
the upper limit of PID control
Output when forward rotation is performed in
PID control.
Used when the bypass-inverter switchover
function is used.
Output at the time of a fan alarm.
Output when the heatsink temperature
reaches about 85% of the heatsink overheat
protection operation temperature.
Output when the inverter is running and start
command is on.
Output when the power failure-time
deceleration function is executed.
(retained until release)
Output during PID control.
Output when the absolute value of deviation
exceeds the limit value.
Output during retry processing.
Output when the PID output interruption
function is executed.
Used when using advanced PID control
(pump function).
Output in pulses every time the accumulated
output power of the inverter reaches the
Pr.799 setting.
Output during power failure or under voltage
of AC power.
Output when any of the control circuit
capacitor, main circuit capacitor and inrush
current limit circuit or the cooling fan
approaches the end of its service life.
Output when a fault occurs due to the
internal circuit failure of inverter wiring
mistake.
Function assignment of external
Operation
terminal and control
Related
Refer
Parameters
to Page
Pr. 127 to Pr. 134,
219
Pr. 575 to Pr. 577
Pr. 135 to Pr. 139,
231
Pr. 159
Pr. 244
250
276
118
Pr. 261 to Pr. 266
140
Pr. 127 to Pr. 134,
219
Pr. 575 to Pr. 577
Pr. 127 to Pr. 134,
Pr. 241, Pr. 553, Pr.
219
554, Pr. 575 to Pr.
577, C42 to C45
Pr. 65 to Pr. 69
143
Pr. 127 to Pr. 134,
219
Pr. 575 to Pr. 577
Pr. 575 to Pr. 591
236
Pr. 799
124
Pr. 30, Pr. 70
102
Pr. 255 to Pr. 259
251
119
117
4

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents