Troubleshooting Problems With Outdoor Unit Transmission Power Supply Circuit - Mitsubishi Electric PURY-HP72 Service Handbook

R410a
Hide thumbs Also See for PURY-HP72:
Table of Contents

Advertisement

[8-12 Control Circuit (TKMU) ]
8-12-2
Troubleshooting Problems with Outdoor Unit Transmission Power Supply
Circuit
1) PURY-HP72, HP96TKMU-A-H
Check the voltage at the indoor/outdoor
transmission terminal block (TB3) of outdoor unit.
Check the voltage at TB3 after removing transmission
line from TB3.
Check whether the male connector is connected to
the female power supply connector (CN40).
NO
Check voltage of terminal block for centralized control (TB7).
Check voltage of TB7 by removing transmission line from TB7.
Check the voltage between No.1 and No.2 pins of the
CN62 on the control board.
Check the voltage between No.1 and No.2 pins of the
CN62 on the power supply board for the transmission line.
Check the voltage between No.1 and No.3 pins of
the CNDC3 on the INV board.
Check the voltage between TB31 and TB42 on the noise filter.
Check the voltage between the + and – terminals
on the diode stack.
Check the voltages among TB21, TB22, and
TB23 on the noise filter.
Check the voltage at the power supply terminal block TB1.
HWE13080
YES
DC 24 ~ 30 V
NO
YES
DC 24 ~ 30 V
NO
Connected
YES
YES
DC24 ~ 30V
NO
NO
YES
DC24 ~ 30V
NO
YES
DC24 ~ 30V
NO
YES
DC24 ~ 30V
NO
NO
YES
DC265 ~ 357V
NO
YES
DC265 ~ 357V
NO
YES
DC265 ~ 357V
NO
YES
AC188 ~ 253V
NO
YES
AC188 ~ 253V
NO
Check whether the transmission line is disconnected,
check for contact failure, and repair the problem.
Check if the indoor/outdoor transmission line is not
short-circuited, and repair the problem.
Check the wiring between the control board and power supply board
for the transmission line (CN62, CNPS, CN102 and CNIT),
and check for proper connection of connectors.
YES
Is there a wiring
Fix the wiring and connector
error or a connector
disconnection.
disconnection?
Check for shorted transmission
line for centralized control.
Replace the control board.
YES
Is there a connector
Fix the connector disconnection.
disconnection?
NO
Check the voltage between No.5 and No.2 pins
of the CNPS on the control board.
YES
Is the voltage
Replace the M-NET board
measurement between
4.5 and 5.2 VDC?
Replace the M-NET board
Replace the INV board.
Replace the noise filter.
Replace the diode stack.
Replace the noise filter.
Check and fix any power supply wiring and main power
supply problems found.
- 308 -