Error Codes [4250, 4255] Detail Code 104 - Mitsubishi Electric PURY-HP72 Service Handbook

R410a
Hide thumbs Also See for PURY-HP72:
Table of Contents

Advertisement

[7-6 Error Code Definitions and Solutions: Codes [4000 - 4999] ]
7-6-25

Error Codes [4250, 4255] Detail Code 104

1. Error code definition
Short-circuited IPM/Ground fault (Detail code 104)
2. Error definition and error detection method
When IPM/IGBT short damage or grounding on the load side is detected just before starting the inverter.
3. Cause, check method and remedy
In the case of 4250
Cause
(1)
Grounding fault
compressor
(2)
Inverter output
related
In the case of 4255
Cause
(1)
Grounding fault
of fan motor
(2)
Fan board fail-
ure
For inverter-related error codes, refer to the following page(s).
[8-10 Troubleshooting Inverter Problems (TKMU)](page 288)
[8-11 Troubleshooting Inverter Problems (YKMU)](page 298)
HWE13080
Check method and remedy
Refer to the following page(s).
(TKMU)
[8-10-3 Checking the Compressor for Ground Fault and Coil Resistance Problems](page
290)
(YKMU)
[8-11-3 Checking the Compressor for Ground Fault and Coil Resistance Problems](page
300)
Refer to the following page(s).
(TKMU)
[8-10-2 Checking the Inverter Board Error Detection Circuit](page 290)
[8-10-3 Checking the Compressor for Ground Fault and Coil Resistance Problems](page
290)
[8-10-4 Checking the Inverter for Damage at No-Load](page 290)
[8-10-5 Checking the Inverter for Damage during Compressor Operation](page 291)
[8-10-10 Checking the Installation Conditions](page 293)
(YKMU)
[8-11-2 Checking the Inverter Board Error Detection Circuit](page 300)
[8-11-3 Checking the Compressor for Ground Fault and Coil Resistance Problems](page
300)
[8-11-4 Checking the Inverter for Damage at No-Load](page 300)
[8-11-5 Checking the Inverter for Damage during Compressor Operation](page 301)
[8-11-10 Checking the Installation Conditions](page 303)
Check method and remedy
Refer to the following page(s).
(TKMU)
[8-10-6 Checking the Fan Motor for Ground Fault and Coil Resistance Problems](page 291)
(YKMU)
[8-11-6 Checking the Fan Motor for Ground Fault and Coil Resistance Problems](page 301)
Refer to the following page(s).
(TKMU)
[8-10-7 Checking the Fan Board Error Detection Circuit at No Load](page 291)
[8-10-8 Checking the Fan Inverter for Damage at No Load](page 292)
[8-10-9 Checking the Fan Inverter for Damage with Load](page 293)
(YKMU)
[8-11-7 Checking the Fan Board Error Detection Circuit at No Load](page 301)
[8-11-8 Checking the Fan Inverter for Damage at No Load](page 302)
[8-11-9 Checking the Fan Inverter for Damage with Load](page 303)
- 207 -
GB

Hide quick links:

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the PURY-HP72 and is the answer not in the manual?

Questions and answers

roque
March 14, 2025

what is the set up mode for recovery, and charging of sys?

Ariel Lituma
April 15, 2025

Why can control my indoor unit with centralize control

1 comments:
Mr. Anderson
April 15, 2025

You may not be able to control your Mitsubishi Electric PURY-HP72 indoor unit with centralized control for the following reasons:

1. The power jumper connector on the outdoor unit may not be correctly set. It should be connected to CN40 on only one outdoor unit.

2. The central control switch (SW5-1) on the control board of all outdoor units must be set to "ON."

3. Address settings may not be correctly configured. The main indoor unit should be assigned the smallest address (e.g., IC00), and correct port number settings are required.

4. If using a remote controller alone, an interlock setting from the remote controller is needed.

5. Both ME and MA remote controllers cannot be connected to the same indoor unit group.

6. System controller power issues may occur if the outdoor unit fan rotates due to external forces, causing the system controller to detect an error.

7. Improper wiring or incorrect voltage at TB7 may also prevent operation.

Check each of these conditions to ensure proper centralized control.

This answer is automatically generated

Ariel Lituma
April 15, 2025

Why can’t control indoor unit with centralize control and stay the MA control set up can’t. Control the mode

1 comments:
Mr. Anderson
April 15, 2025

The Mitsubishi Electric PURY-HP72 indoor unit cannot be controlled with centralized control and the mode control setup does not function due to the following reasons:

1. Central control is not possible if the indoor/outdoor transmission line is used, even if TB7 terminals are daisy-chained.
2. Shielded cables must be used, and the connection must only be made after confirming the voltage is below 20 VDC.
3. Improper connection of the transmission line for centralized control, such as not correctly daisy-chaining terminals M1 and M2 or not short-circuiting the earth and S terminals on TB7.
4. If a power supply unit is not connected to the centralized control line, the power jumper connector must be moved from CN41 to CN40 on one outdoor unit—if this is not done, mode control will not function.
5. Overlapped indoor unit addresses or noise interference on the remote controller lines can also prevent proper control.
6. Failure to set one MA remote controller to MAIN or exceeding its capacity can result in control failure.

All these factors must be correctly configured for centralized and mode control to function properly.

This answer is automatically generated

Table of Contents

Save PDF