[7-6 Error Code Definitions and Solutions: Codes [4000 - 4999] ]
7-6-11

Error Codes [4220, 4225] Detail Code 109 (TKMU)

1. Error code definition
Abnormal bus voltage rise (Detail code 109)
2. Error definition and error detection method
If Vdc
400V is detected during inverter operation.
3. Cause, check method and remedy
(1) Different voltage connection
Check the power supply voltage on the power supply terminal block (TB1).
(2) INV board failure
If the problem recurs, replace the INV board or fan board.
In the case of 4220: INV board
In the case of 4225: Fan board
For inverter-related error codes, refer to the following page(s). [8-10 Troubleshooting Inverter Problems (TKMU)](page 288)
7-6-12

Error Codes [4220, 4225] Detail Code 109 (YKMU)

1. Error code definition
Abnormal bus voltage rise (Detail code 109)
2. Error definition and error detection method
If Vdc
830V is detected during inverter operation.
3. Cause, check method and remedy
(1) Different voltage connection
Check the power supply voltage on the power supply terminal block (TB1).
(2) INV board failure
If the problem recurs, replace the INV board or fan board.
In the case of 4220: INV board
In the case of 4225: Fan board
For inverter-related error codes, refer to the following page(s). [8-11 Troubleshooting Inverter Problems (YKMU)](page 298)