Indoor Unit Installation Location; Outline Dimensions; Service Space - Mitsubishi Electric PLH-2 Installation Manual

Air-conditioners
Hide thumbs Also See for PLH-2:
Table of Contents

Advertisement

D
A
D
B
C
F
E

2.1. Outline dimensions

Mount the indoor unit on a wall strong enough to withstand the weight
of the unit.
Select a location so that air can be blown into all corners of the room.
Avoid locations exposed to outside air.
Select a location free of obstructions to the airflow in and out of the
unit.
Avoid locations exposed to steam or oil vapour.
Avoid locations where combustible gas may leak, settle or be gener-
ated.
W
Avoid installation near machines emitting high-frequency waves (high-
frequency welders, etc.)
Avoid locations where the airflow is directed at a fire alarm sensor.
(Hot air could trigger the alarm during the heating operation.)
Avoid places where acidic solutions are frequently handled.
Avoid places where sulphur-based or other sprays are frequently used.

2.2. Service space

Select ideal blowing direction according to the shape of room and in-
stalling position.
A Ceiling
B Ceiling panel
C Obstacle
D 1 m or more
E 50 cm or more (Entire periphery)
F Panel
Reserve the above mentioned space for doing the piping and wiring
work, as well as for the maintenance work which is done from the
bottom & left/right sides. Similarly, reserve as much space as possible
to facilitate work & safety at the time of suspending.
E

2. Indoor unit installation location

Models
W
D
PLH-2, 2.5
760
760
(mm)
H
307
7

Advertisement

Table of Contents
loading

This manual is also suitable for:

2.5kkcMr.slim plh-2kkcMr.slim plh-2.5kkc

Table of Contents