Test Run - Mitsubishi Electric PLH-2 Installation Manual

Air-conditioners
Hide thumbs Also See for PLH-2:
Table of Contents

Advertisement

A
A
B
C
D
E

8. Test run

E
8.3. Self-diagnosis
C For available LED displays (LEDs 1, 2) on the indoor unit board,
refer to the table below.
LED2 (Microprocessor
Should remain ON always to indicate the con-
power supply)
trol power supply is turned ON.
Lights up to indicate the power is connected
to the wired remote controller.
LED1 (Remote control-
Lights up only for the indoor unit connected to
ler power supply)
the outdoor unit address "0".
A The temperature code is indicated by numbers 1 through 15 which
°
°
represent -40
to 90
C.
Check the compressor operation by confirming that the code
number decreases when cooling and increases when heating.
Code
1
Indoor coil temperature -40°C ~ 1°C 2°C ~ 10°C 11°C ~ 15°C 16°C ~ 20°C
Code
5
Indoor coil temperature 21°C ~ 25°C 26°C ~ 30°C 31°C ~ 35°C 36°C ~ 40°C
Code
9
Indoor coil temperature 41°C~ 45°C 46°C ~ 50°C 51°C ~ 55°C 56°C ~ 60°C
Code
13
Indoor coil temperature 61°C~ 70°C 71°C ~ 90°C
8.4. Check of Drainage
At the of trial run, ensure the water is being properly drained out and
that no water is leaking from joints.
Always make this check at the time of installation during other air-
conditioning (cooling) season.
Similarly, check it also before finishing the ceiling of new premises.
(1) Remove the cover of water supply inlet, and fill in about 1000 cc of
water, using water supply pump, etc. While filling water, ensure that it
is not sprayed into the internal drain lift up mechanism.
(2) Confirm that water is being drained out through the drainage outlet,
after switching over from remote control mode to trial run mode.
(3) After checking, fit back the cover without fail, and cut off the main power
supply switch.
(4) When installing during other than air-conditioning out the water. After
confirming that water drains out, fit back the drain plug.
A Insert the pump end 3 to 5 cm
B Cover of water supply inlet (to remove off its screw & pull it downward)
C About 1000 cc
D Water
E Drain plug
2
3
4
6
7
8
10
11
12
14
15
Sensor malfunction