j. Reinstall blower access d oor i fremoved.
k. Turn gas valve ON/OFF switch t oON.
FURNACE OVERHEATING
HAZARD
Failure
to follow
this
caution
may result
in reduced
furnace life.
Recheck
temperature
rise.
It must
be within
limits
specified on the rating plate. Recommended
operation is
at the midpoint of rise range or slightly above.
6. Set thermostat heat anticipator.
a. Mechanical thermostat - Set thermostat heat anti-
cipator to match the amp. draw of the electrical
components
in the R-W circuit. Accurate amp. draw
readings can be obtained at the wires normally con-
nected to thermostat subbase terminals, R and W.
The thermostat anticipator should NOT be in the
circuit while measuring current. (1 .) Remove ther-
mostat from subbase or from wall. (2.) Connect an
amp. meter as shown in Figure 43 across the R
and W subbase terminals or R and W wires at wall.
(3.) Record amp. draw across terminals when fur-
nace is in heating and after blower starts.
(4.) Set heat anticipator on thermostat per thermo-
stat instructions and install on subbase or wall.
b. Electronic thermostat: Set cycle rate for 4 cycles
per hr.
7. Adjust heat off delay The heat off delay has 4 ad-
justable settings from 90 sec to 180 sec. The heat off
delay jumpers are located on the furnace control board.
(See Figure 25) To change the heat off delay setting,
move the jumper from one set of pins on the control to
the pins used for the selected heat off delay. Factory
heat off delay setting is 120 sec.
8. Set airflow CFM for cooling Select the desired blower
motor speed lead for cooling airflow. See Table 5-Air
Delivery-CFM
(With Filter). See Table 12 for lead color
identification.
Figure 41 - Gas Control Valve
A06666
Figure 42 - Orifice Hole
A93059
Figure 43 -- Amp, Draw Check With Ammeter
SUBBASE
TERMINALS
WITH
THERMOSTAT
REMOVED
(ANITICIPATOR,
CLOCK,
ETC.,
MUST BE OUT OF CIRCUIT.)
AMMETER
10 TURNS
FROM
UNIT 24-V
CONTROL
TERMINALS
EXAMPLE:
5.0AMPSONAMMETER
= 0.5AMPSFORTHERM©STAT
10 TURNS
AROUND
JAWS
ANTiCiPATOR
SETTING
A96316
Step 4--Check
Safety
Controls
The flame sensor, gas valve, and pressure switch were all
checked in the Start-up
procedure section as part of normal
operation.
1. Check Main Limit Switch(es)
This control shuts off combustion
control system and
energizes air-circulating
blower motor, if furnace over-
heats. By using this method to check limit control, it can
be established that limit is functioning properly and will
operate if there is a restricted duct system or motor fail-
ure. If limit control does not function
during this test,
cause must be determined and corrected.
a. Run furnace for at least 5 minutes.
b. Gradually block off return air with a piece of card-
board or sheet metal until the limit trips.
c. Unblock return air to permit normal circulation.
d. Burners will re-light when furnace cools down.
2. Check draft safeguard switch.
The purpose of this control is to cause the safe shut-
down of the furnace during certain blocked vent condi-
tions.
441 01 1402 02