GE 400 User Manual page 58

Sg series 400 & 500 kva / 480vac ul / s2
Hide thumbs Also See for 400:
Table of Contents

Advertisement

Configuration
BATTERY CONFIGURATION
Type
Float voltage
Recharge current
Autonomy time
Stop Operation time
Capacity
: 0250 Ah
ESC
Float voltage
Voltage to maintain battery charging.
Float voltage = Number of battery cells x battery float voltage per cell.
Typical battery float voltage per cell (ask the battery manufacturer for confirmation):
Sealed battery (VRLA):
NiCd without boost-charge:
NiCd with boost-charge:
Open battery without boost-charge:
Open battery with boost-charge:
Recharge current
Maximum battery recharge current.
Max 20% of battery capacity (Ah).
Example: 250Ah - max recharging current 50A.
Autonomy time
The autonomy time of the battery.
UPS autonomy on battery mode at full load condition.
This value is calculated based on the battery type, capacity and number of cells.
Stop Operation time
Residual battery autonomy time before UPS forced shutdown.
Standard set 3 minutes. Settable from 1 minute to autonomy time in minutes (see tables).
Capacity
Ah capacity of the battery.
Cells
Number of cells of the battery, see "Float voltage".
Example:
240 battery cells
NOTE !
The values indicated above, must be considered as standard values.
The actual programmed values must be the ones defined from the battery manufacturer.
Configuration
CONFIGURATION
Save and exit ?
Yes
Modifications reserved
OPM_SGS_USM_M40_M50_2US_V010.doc
BATTERY CONFIGURATION screen
Recharge type
Recharge type (Lead Acid / NiCd / Boost).
:
Lead Acid
:
545 V
Lead Acid
:
050.0 A
:
012 min
:
003 min
NiCd
Cells
: 240
Boost
2.27Vdc for cell
1.41Vdc for cell
1.41 (1.55 boost-charge) Vdc for cell
2.23Vdc for cell
2.23 (2.35 boost-charge) Vdc for cell
40 blocks / 12Vdc battery
CONFIGURATION screen
Screen to save the configuration of set parameters.
Any additional modification of setup parameters can be done
only from a GE SERVICE PERSON as it requires an access code.
for:
Sealed battery (VRLA), NiCd without boost-
charge and open battery without boost-
charge.
for:
Nickel Cadmium battery with boost-charge.
for: O
pen battery with boost-charge.
240 cells x 2.27Vdc = 545Vdc
386 cells x 1.41Vdc = 545Vdc
351 cells x 1.41Vdc = 495 (545) Vdc
240 cells x 2.23Vdc = 535Vdc
232 cells x 2.23Vdc = 518 (545) Vdc
80 blocks / 6Vdc battery
240 blocks / 2Vdc battery
Continue
Page 58/79
User Manual SG Series 400 & 500 UL S2

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

500Sg 400Sg 500