GE 489 Instruction Manual page 200

Generator management relay
Hide thumbs Also See for 489:
Table of Contents

Advertisement

6.3 MODBUS MEMORY MAP
Table 6–2: DATA FORMATS (SHEET 5 OF 5)
FORMAT
TYPE
CODE
F211
Unsigned
16 bit integer
F212
Unsigned
16 bit integer
F213
Unsigned
16 bit integer
F214
Unsigned 16 bit
integer
F215
Unsigned
16 bit integer
F216
Unsigned
16 bit integer
F217
Unsigned
6
16 bit integer
F218
Unsigned
16 bit integer
F219
Unsigned
16 bit integer
F220
Unsigned
16 bit integer
6-38
DEFINITION
Volts/Hertz element type
0 = Curve #1, 1 = Curve #2, 2 = Curve #2, 3 = Definite Time
RTD number
VALUE
PARAMETER
0
All
1
RTD #1
2
RTD #2
3
RTD #3
4
RTD #4
5
RTD #5
6
RTD #6
Communications monitor port selection
0 = Computer RS485, 1 = Auxiliary RS485, 2 = Front Panel RS232
Waveform Memory Channel Selector
VALUE PARAMETER
0
Phase A line current
512 counts = 1 × CT
1
Phase B line current
512 counts = 1 × CT
2
Phase C line current
512 counts = 1 × CT
3
Neutral-end phase A line current
512 counts = 1 × CT
4
Neutral-end phase B line current
512 counts equals 1 × CT
Current Source
0 = Neutral-end CTs; 1 = Output-end CTs
DNP Port Selection
0 = None, 1 = Computer RS485, 2 = Auxiliary RS485, 3 = Front Panel RS485
Ground Directional MTA
0 = 0°, 1 = 90°, 2 = 180°, 3 = 270°
Breaker State
0 = 52 Closed, 1 = 52 Open/Closed
Step Up Transformer Type
0 = None, 1 = Delta/Wye
IRIG-B Type
0 = None, 1 = DC Shift, 2 = Amplitude Modulated
489 Generator Management Relay
6 COMMUNICATIONS
VALUE
PARAMETER
7
RTD #7
8
RTD #8
9
RTD #9
10
RTD #10
11
RTD #11
12
RTD #12
VALUE PARAMETER
5
Neutral-end phase C line current
512 counts = 1 × CT
6
Ground current
512 counts = 1 × CT
7
Phase A to neutral voltage
3500 counts = 120 secondary volts
8
Phase B to neutral voltage
3500 counts = 120 secondary volts
9
Phase C to neutral voltage
3500 counts = 120 secondary volts
GE Multilin