4.13 S12 TESTING
PATH: SETPOINTS
S12 TESTING

FAULT SETUP

[ENTER] for more
4
The values entered here are substituted for the measured values in the 489 when the
4-80
FAULT SETUP
ð
FAULT Iphase
ENTER
ð
OUTPUT: 0.00 x CT
ESCAPE
FAULT VOLTAGES
ESCAPE
PHASE-N: 1.00 x Rated
MESSAGE
FAULT CURRENT
ESCAPE
LAGS VOLTAGE:
MESSAGE
FAULT Iphase
ESCAPE
NEUTRAL: 0.00 x CT
MESSAGE
FAULT CURRENT
ESCAPE
GROUND: 0.00 x CT
MESSAGE
FAULT VOLTAGE
ESCAPE
NEUTRAL: 0 Vsec
MESSAGE
FAULT STATOR
ESCAPE
RTD TEMP: 40°C
MESSAGE
FAULT BEARING
ESCAPE
RTD TEMP: 40°C
MESSAGE
FAULT OTHER
ESCAPE
RTD TEMP: 40°C
MESSAGE
FAULT AMBIENT
ESCAPE
RTD TEMP: 40°C
MESSAGE
FAULT SYSTEM
ESCAPE
FREQUENCY: 60.0 Hz
MESSAGE
FAULT ANALOG
ESCAPE
INPUT 1: 0%
MESSAGE
FAULT ANALOG
ESCAPE
INPUT 2: 0%
MESSAGE
FAULT ANALOG
ESCAPE
INPUT 3: 0%
MESSAGE
FAULT ANALOG
ESCAPE
INPUT 4: 0%
MESSAGE
489 Generator Management Relay
Range: 0.00 to 20.00 × CT in steps of 0.01
Range: 0.00 to 1.50 × Rated in steps of 0.01
Entered as a phase-to-neutral quantity.
Range: 0 to 359° in steps of 1
Range: 0.00 to 20.00 × CT in steps of 0.01
180° phase shift with respect to Iphase OUTPUT
Range: 0.00 to 20.00 × CT in steps of 0.01
CT is either XXX:1 or 50:0.025
Range: 0.0 to 100.0 Vsec in steps of 0.1
Fundamental value only in secondary volts
Range: –50 to 250°C in steps of 1
Range: –50 to 250°C in steps of 1
Range: –50 to 250°C in steps of 1
Range: –50 to 250°C in steps of 1
Range: 5.0 to 90.0 Hz in steps of 0.1
Range: 0 to 100% in steps of 1
Range: 0 to 100% in steps of 1
Range: 0 to 100% in steps of 1
Range: 0 to 100% in steps of 1
SIMULATION MODE
4 SETPOINTS
4.13.3 FAULT SETUP
is "Simulate Fault".