CHAPTER 4: CONNECTING TO DEVICES AND NETWORKS

Network connections

To connect the D400
to network devices

Front network port

To connect a local PC
to the D400
D400 SUBSTATION GATEWAY USER'S MANUAL
Table 14: Fiber Optic Connector Signal Definitions
Connector
Function
TX1
Primary Fiber Optic Transmit Port
RX1
Primary Fiber Optic Receive Port
TX2
Hot Standby Secondary Fiber Optic Transmit Port
RX2
Hot Standby Secondary Fiber Optic Receive Port
See "10Base-FL hot standby fiber optic ethernet switch" on page 46 or "100Base-FX hot
standby fiber optic ethernet adapter" on page 47 for more information.
The D400 supports a network interface through Ethernet connections to the 4-Port
Twisted-Pair Ethernet Switch or Redundant Twisted-Pair Ethernet + COM2 Port Adapter.
Within the operating system of the D400, the card in slot 11 is assigned to Ethernet
interface eth0 and the card in slot 12 is assigned to Ethernet interface eth1.
All RJ-45 connectors have the same signal definition. However, the rear Ethernet ports are
auto MDI/MDIX and can support a straight-through or crossover cable.
See "4-Port twisted-pair ethernet switch" on page 45 and "Redundant twisted-pair
ethernet + COM2 port adapter" on page 49 for more information.
Plug network cables into the D400 Ethernet ports.
Figure 37: D400 Ethernet ports
If the D400 is deployed in the presence of strong RF energy in the 110 MHz to 125 MHz
band, such as airport Instrument Landing System (ILS) localizers or aviation radio
transmitters, it is recommended that shielded twisted-pair Ethernet cables be used.
To access the D400's HMI, a local or portable PC can be directly connected to the network
port located on the front panel of the D400.
The front network port is tied to the network interface card in the NET1 slot (slot 11) (eth0
for configuration purposes in a single Ethernet configuration or eth1 for dual Ethernet
configuration).
Connect the supplied straight-through Ethernet cable (GE Item No. 977-0209LF) to your
computer's network communications port and to the D400's front Ethernet port. Older
computers without auto MDIX Ethernet capability may require an Ethernet cross-over
cable.