4.2.10 Jog operation (Pr. 15, Pr. 16)

Pr. 15 "jog frequency"
Pr. 16 "jog acceleration/deceleration time"
In external operation mode, jog operation can be started and stopped by the start signal (STF, STR) with the
jog signal ON, after selection of the jog operation function using the input terminal function selection. In the
PU operation mode, jog operation can also be performed using the PU (FR-DU04/FR-PU04).
Set the frequency and acceleration/deceleration time for jog operation
Parameter Number
Factory Setting
15
16
Note: 1. In S-shaped acceleration/deceleration pattern A, the set time is a period of time required to reach
Pr. 3 "base frequency".
2. The acceleration time and deceleration time cannot be set separately for jog operation.
3. The value set in Pr.15 "jog frequency" should be equal to or greater than the Pr.13 "starting
frequency" setting.
4. When Pr. 79 Operation mode selection="4", push
make a start or push
Setting Range
5Hz
0 to 400Hz
0 to 3600 s
0.5 s
0 to 360 s
Output frequency (Hz)
Pr.20
Jog frequency
Pr.15
setting range
JOG signal
Forward rotation STF
Reverse rotation STR
STOP
to make a stop.
RESET
Related parameters
Pr. 20 "acceleration/deceleration
Pr. 21 "acceleration/deceleration time
Pr. 79 "operation mode selection"
Pr. 180 to Pr. 186
(input terminal function selection)
Remarks
When Pr. 21 = 0
When Pr. 21 = 1
Forward
rotation
Reverse
rotation
Pr.16
ON
ON
ON
/
FWD
REV
80
PARAMETERS
reference frequency"
increments"
Time
of the PU (FR-DU04/FR-PU04) to