4.2.65 Capacitor life alarm (Pr. 503, Pr. 504)

Pr. 503 "capacitor life timer"
Pr. 504 "capacitor life alarm output setting time"
When the cumulative operation time of the inverter has elapsed the time set in Pr. 504 "capacitor life alarm
output set time", the capacitor life alarm output signal "Y95" is output to inform that it is time for replacement
(Note 1) of the smoothing capacitor in the main circuit of the inverter.
Parameter Number
503
504
<Setting>
Parameter Number
503
(0 to 999800h)
504
First power ON
Maintenance timer
(Pr. 503)
Y95 output / display
The life of electrolytic capacitor is about ten years (87600 hours) in the average yearly ambient temperature
of 40 ° C. (Note 2)
The life of electrolytic capacitor decreases to half if the ambient temperature increases by 10 ° C and doubles
if decreases by 10 ° C. Please note this as reference when setting the time.
For example, when the average yearly ambient temperature is 50 ° C, set "438" (43800 hours) in Pr. 504
Note: 1. For replacement of the capacitor, contact the nearest Mitsubishi FA center.
2. The estimated life time (87600 hours) of the capacitor differs according to the environmental
conditions (ambient temperature, conditions, etc.) of the inverter.
Pr. 611
Refer to Pr. 57.
Factory Setting
Setting range
-
876
0 to 9998, (9999)
(87600h)
Setting
Description
Display the cumulative operation time
of the inverter in 100hours increments.
-
(write is not enabled)
Clamped at 9998 (999800h)
0 to 9998
Set the time until the capacitor life
alarm output signal "Y95" is output.
Set by the manufacturer. The set time
9999
is a factory setting value.
OFF
Related parameters
Pr. 190 to Pr. 195
(output terminal function selection)
-
The capacitor life is counted every
1hours and the figures above
By setting "95" (negative logic 195) in
Pr. 190 to Pr. 195 "output terminal
function selection", the capacitor life
alarm signal "Y95" can be output.
(Refer to page 158 .)
Pr. 504
ON
182
PARAMETERS
Remarks
hundreds are displayed.
999800h