2000 Series | Program Entry Guide | 4.0
Table 2: continued
Modem II Report
POINT BYPASS POINT
001 (-024)
RAM ACCESS OK
RAM ACCESS FAIL
RESTORAL REPORT
POINT 001 (-024)
RE-BOOT
RF BATTERY LOW POINT
001 (-024)
RF BATT RESTORE
POINT 001 (-024)
RF Rcvr Tamper
SDI 7 (8)
RF Rcvr Tamper
Restoral
SDI 7 (8)
RF Rcvr Trouble
Device 7 (8)
RF Rcvr Trbl
Restoral
Device 7 (8)
RF TAMPER TROUBLE
RF TAMPER RESTORAL
SERVICE START
SERVICE STOP
SWINGER BYPASS POINT
001 (-024)
TEST REPORT
TROUBLE REPORT POINT
001 (-024)
USR CODE TAMPER
WATCHDOG RESET
0101
0101
If you choose Modem Format, go to Section 5.0 Remote Programming. The prompts in the remainder
0101
of the Receiver Group have no meaning for the Modem Format.
Bosch Security Systems | 7/05 | 35114F
Receiver
Description
Point 1 to 24 bypassed. Points can be bypassed from the keypad or from a remote
programmer. Bypass Reports are only sent when Opening and Closing Reports are enabled in
Section 6.0 Open/Close.
Normal remote programmer session termination.
Remote programmer made connection with control panel, but passcode was incorrect, or call
was not terminated with a Good-bye or Reset-Bye.
Restoral Report from Points 1 to 24.
Control panel reset with the standby pin (Refer to Installation Manual) or a remote
programmer.
Low battery in RF sensor, keypad, or arming device.
Restored battery in RF sensor, keypad, or arming device.
Enclosure tamper from premises RF receiver (D208RF, D216RF).
SDI number is the device address (7 or 8). Refer to Section 10.0 Address Configuration.
Enclosure tamper restoral from premises RF receiver (D208RF, D216RF).
SDI number is the device address (7 or 8). Refer to Section 10.0 Address Configuration.
Trouble from premises RF receiver (D208RF, D216RF)
SDI number is the device address (7 or 8). Refer to Section 10.0 Address Configuration.
Restoral from premises RF receiver (D208RF, D216RF)
SDI number is the device address (7 or 8). Refer to Section 10.0 Address Configuration.
Tamper RF point, Controlled point, system off.
Tamper restoral, RF point.
Installer mode entered (Stand-by locked down, installer passcode entered).
Installer mode exited.
Points 1 to 24 bypassed automatically by the system after four alarms or troubles in one armed
or disarmed period. You can program the Swinger Bypass feature to activate after less than
four alarms or troubles. Refer to Swinger Count prompt in Section 1.0 System Configuration.
Use the point code to program this feature by point. Refer to Section 11.0 Point Codes.
Automatic Test Timer Report.
Trouble on Points 1 to 24, Fire and Non-fire combined.
This report transmitted after six attempts to enter an invalid passcode.
System automatically reset. Call Bosch Security Systems if reports persist.