System Connectors - GE HOME GENERATOR 10000 WATT Installation And Start-Up Manual

10,000 watt home generator system
Hide thumbs Also See for HOME GENERATOR 10000 WATT:
Table of Contents

Advertisement

Available languages

Available languages

system connectors

Low Voltage connections to signal fault contacts, transfer switch communication, remote LED and auxiliary 12VDC power are
made via a removable ten-pole connector plug. Compare this illustration with your generator to familiarize yourself with the
location of these connections. Count down to the proper pin location on the control board since visual alignment with the decal
can be misleading:
a - fault contacts — Use NO, COM and NC to hook up a
siren, light, etc. to alert you in case of a fault. Contacts
reverse state (NO goes to NC and vice versa) upon a fault
condition.
B - transfer switch communication — Connect to transfer
switch control board for communication interface using
18AWG copper twisted pair wire.
c - remote LeD output — Use this to hook up the remote
LED supplied with the generator. The remote LED will
turn on and off in a series of blinks if certain faults are
detected in the generator.
• For power output connection, use #8 AWG minimum 300 volt 75°C-90°C copper wire, (ref. NEC Table 310.16, 100 ft.
Use National Electric Code for correction factors and wire size calculations.)
• For Utility Circuit connection use #14 AWG minimum 300 volt 75°C-90°C copper wire
• For transfer switch communication use #18 AWG twisted pair conductors, no greater than 200 ft in length, 300 volt
75°C-90°C copper wire
• When connecting to the connector plugs, fasten only one wire to each connector screw.
• Torque connector plug screws to 7 in-lb (7.9 Newton meter).
B
D
A
C
E
D - +12 Volt Dc, .5 amp output — Internal power supply.
e - 240 Volt utility — Use to hook up the 240V utility leads
from the transfer switch to the generator.
f – ten-pole connector Plug
G – two-pole connector Plug
F
G