4.5 Acceptance Criteria

Install and accept the ESM to ensure that the ESM can work properly.
No.
1
2
3
Issue 03 (2020-01-08)
Parameter
Equalized charge voltage
Float charge voltage
Low voltage alarm
Load low voltage disconnection (LLVD)
threshold
Battery low voltage disconnection (BLVD)
threshold
Check Item
Acceptance Criteria
Indicator
The indicator status is normal (the RUN indicator is steady on and
status
no indicator is red).
Working
You are advised to simulate mains disconnection or connection.
status
The working status of the ESM is normal after the mains
disconnection or connection.
Current
The ESM current is normal. According to system settings, the
current deviation is within ± 2 A.
Copyright © Huawei Technologies Co., Ltd.
4 Installation and Commissioning
Standard Value
53.5 V
53.4 V
47 V
46 V
44 V