5.2

Explanation of parameters

Diagnostics: No supply voltage L+
Enabling of the diagnostics for no or insufficient supply voltage L+.
Diagnostics: Short circuit to ground
Enabling of the diagnostics if a short circuit of the actuator supply to ground occurs.
Diagnostics: Short circuit to L+
Enabling of the diagnostics if a short circuit of the actuator supply to L+ occurs.
Check for wire break
Determines whether a check for wire break is carried out for the channel. The wire break
diagnostics for the channel can only be reported with activated check for wire break. The
measuring current for the channel is disabled with deactivated check for wire break.
Diagnostics: Wire break
Enabling of the diagnostics if the line to the actuator is broken. If the wire break diagnostics is
enabled, the parameter "Check for wire break" must also be activated for the channel.
Channel activated
Determines whether a channel is activated or deactivated.
Reaction to CPU STOP
Determines the behavior of the module in the event of a CPU STOP.
Digital output module DQ 16x24VDC/0.5A HF (6ES7132-6BH00-0CA0)
Equipment Manual, 01/2024, A5E52818470-AA
Parameters/address space
5.2 Explanation of parameters