X21 EP terminals

Smart Line Modules 5 kW and 10 kW
Table 4- 66
X21 EP terminal for Smart Line Modules 5 kW and 10 kW
Terminal
1
2
3
4
Type: Screw terminal 1 (Page 755)
Max. cross-section that can be connected: 1.5 mm
Terminals X21.1 and X21.2
Note
Wiring to a digital input of the Control Unit
Output terminal X21.1 must be wired to a digital input on the CU. The drives supplied with
power from the Smart Line Module have to use this signal as a ready signal. This ensures
that a pulse enable can only be issued for the drives (motor or generator operation) when the
infeed is ready.
If interconnection with a digital input on the CU is not possible, the signal must be evaluated
by a higher-level control system instead. It is not permissible that the control system sets the
drives to ready until the infeed "Ready" signal is present.
Booksize Power Units
Manual, (GH2), 04/2014, 6SL3097-4AC00-0BP6
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Designation
DO: Ready
DO: Prewarning
EP +24 V (pulse enable)
EP M (Enable Pulses)
2
4.8 Smart Line Modules with internal air cooling
Technical data
Feedback signal: Smart Line Module ready
The signal switches to high level when the following
conditions have been met:
Electronics power supply (X24) OK
DC link is precharged
Pulses enabled (X21.3/4)
No overtemperature
No overcurrent
DO: Prewarning
High = no prewarning
Low = prewarning
Overtemperature warning threshold/I
5 kW
prewarning: 64 °C, overtemperature threshold: 69 °C
10 kW
prewarning: 68 °C, overtemperature threshold: 73 °C
No regenerative feedback capability due to a line fault
[only monitored when feedback is activated (see
terminal X22.2)]
Voltage 24 V DC
Current consumption: 10 mA
Isolated input
Line Modules Booksize
t
2
281