Operation - Siemens RPM Installation Instructions Manual

Remote printer module
Table of Contents

Advertisement

OPERATION

Controls and Indicators
Siemens Industry, Inc.
Building Technologies Division
When a system event occurs, the PMI/PMI-2/PMI-3 (XLS), FCM2041-U2 (Desigo Fire
Safety Modular), FCM2041-U3 (Cerberus PRO Modular) sends a print message to the
RPM via HNET. The RPM is responsible for printing the message. The RPM contains a
buffer to ensure that events that occur at a rate faster than the PAL -1 can print them are
not lost.
If the FSI option is selected (via
Zeus) the same event is sent to
the FSI port. This event remains
in a buffer until the Foreign
System removes it.
The RPM continuously moni-
tors the connection to the PAL -
1 checking for any errors that
would inhibit printing. Any
errors that are detected are
communicated to the PMI/PMI-
2/PMI-3 (XLS), FCM2041-U2
(Desigo Fire Safety Modular),
FCM2041-U3 (Cerberus PRO
Modular) via HNET for annun-
ciation. Restoration to the
normal condition is also
detected and communicated to
the PMI/PMI-2/PMI-3 (XLS),
FCM2041-U2 (Desigo Fire
Safety Modular), FCM2041-U3
(Cerberus PRO Modular). Print
messages that arrive at the RPM
during a printer fault are stored in the buffer.
The HNET side panel of the RPM contains one reset switch, three LEDs, one termina-
tion switch and one HNET address switch as shown in Figure 2.
A reset switch is located on the top of the panel.
Pushing the reset switch
re-initializes the RPM
operation.
POWER
CPU FAIL
HNET FAIL
A three-position switch located directly beneath the LEDs on the HNET side of the
RPM is used to set the HNET network address of the RPM.
RESET
POWER
CPU FAIL
HNET FAIL
+
+
+
3
1
2
-
-
-
HNET ADDRESS
TERMINATION
6
5
4
HNET
3
2
1
CHASSIS GND
3
-
2
24V INPUT
1
+
HNET SIDE
Figure 2
RPM Side Panel Detail
(Green)
Normally ON. When illuminated, indi-
cates that power for the RPM is applied
to the module.
(Yellow)
Normally OFF . When illuminated, indi-
cates that the module microprocessor
has failed.
(Yellow)
Normally OFF . When illuminated, indi-
cates that the HNET communication with
the RPM has terminated.
2
PORT 3
SPP
RXD
TXD
PORT 1
GND
RS-232
RTS
CTS
RXD
TXD
PORT 3
GND
RS-232
RTS
CTS
RCV+
RCV-
PORT 2
XMIT+
RS-485
XMIT-
GND
PORT 2
SELECT
PRINTER SIDE
P/N 315-033270-12