[ VII Control ]
VII Control

[1] Functions and Factory Settings of the Dipswitches

1. Priority order of the water-temperature-setting-input-signal sources
Water temperature can be controlled by using the signals from the four types of input sources listed below.
The setting for the item with higher priority will override the settings for the items with lower priorities.
The water temperature will be controlled according to the temperature setting in the "Target water temperature" column that
corresponds to a specific combination of the settings for the four items.
No-voltage contact input K91-K93 ON: Heating (EAHV)
Priority 1
Priority 2
No-voltage contact
Analog input or
input K40-K41
(SW 5-9: ON)
Anti-freeze
ON
Ineffective
SW5-7: ON
OFF
SW5-7: OFF
*1 This mode is disabled in EAHV.
*2 EAHV can also set Cooling.
*3 AE-200 and BMS cannot both be simultaneously connected. Only connect one or the other.
No-voltage contact input K91-K93 OFF: Cooling (EAHV, EACV)
* When the operation mode is Cooling, K40-K41 (Anti-freeze) and K40-K42 (Mode change) are disabled.
Priority 1
Priority 2
No-voltage contact
Analog input or
input K01-K03
BMS
Mode Change
(SW5-9: ON)
(Cooling ECO)
SW5-7: ON
Ineffective
ON (Cooling ECO)
SW5-7: OFF
OFF (Cooling)
*1 This mode is disabled in EACV.
*2 EAHV can also set Heating or Heating ECO.
*3 AE-200 and BMS cannot both be simultaneously connected. Only connect one or the other.
Priority order of the operation signal sources
Unit operation (Run/Stop)
Operation mode
Fan mode
(The contact ON has priority.)
*1 When the Anti-freeze contact is ON during heating operation, the setting change is ineffective.
*2 Changing by contact is effective during cooling operation.
*3 Changing by contact is effective during heating operation.
HWE20010
Priority 3
No-voltage contact
input K40-K42
BMS
Mode change
Ineffective
Ineffective
ON
(Heating ECO)
OFF
(Heating)
Remote controller PAR-W31MAA
Input from centralized controller AE-200 or BMS (*3)
No remote controller
-
-
When no RC is used
-
-
-
-
-
Cooling *1
Cooling ECO *1*2
Heating *1
Heating ECO *1*3
Anti-freeze *3
Priority 4
Remote controller PAR-W31MAA
Input from centralized controller AE-200 or BMS (*3)
No remote controller
Manual setting
-
Ineffective
-
Ineffective
-
Ineffective
When no RC is used
-
-
Anti-freeze
-
Heating ECO
-
Heating
-
Cooling (*1)
-
-
Priority 3
Manual setting
Schedule setting
Ineffective
Ineffective
Ineffective
Ineffective
-
Anti freeze (*1)
Heating ECO (*1)
Heating (*1)
Cooling
When schedule has
-
been set (*2)
Remote controller
No-voltage contact
PAR-W31MAA
The last setting has priority.
The last setting has priority.
OFF
Cooling ECO can not be set from the remote controller or the
centralized controller.
ON
The last setting has priority.
OFF
ON
OFF
ON
OFF
ON
- 83 -
Schedule setting
Ineffective
Ineffective
Ineffective
-
-
-
-
-
When schedule has
been set (*2)
Target water temperature
Temperature setting for the
analog signal input
Cooling ECO
-
Cooling
-
25ºC
-
Heating ECO
-
Heating
-
Cooling
Target water temp is controlled
according to the setting on the
remote controller.
Input from centralized
controller AE-200 or BMS
The last setting has priority.
Ineffective
The last setting has priority.
Ineffective
The last setting has priority.
Ineffective
Target water temperature
25ºC
Temperature setting for
the analog signal input
Heating ECO
Heating
25ºC
Heating ECO
Heating
Cooling
Target water temp is
controlled according to
the setting on the remote
controller.