Air conditioning control system
Hide thumbs Also See for EB-50GU-A:

Advertisement

Air Conditioning Control System
Centralized Controller
EB-50GU-A/EB-50GU-J
-Web Browser for System Maintenance Engineer-
Before using the controller, please read this Instruction Book carefully to ensure proper operation.
Retain this manual for future reference.
Contents
1. Introduction ...........................................................................2
1-1. Terms Used in This Manual .........................................................2
1-2. PC Requirements .........................................................................2
2. Setting the Operating Environment ......................................3
2-1. Setting the IP Address of the PC .................................................3
2-2. Setting the Web Browser .............................................................5
Engineer ...............................................................................8
4. Monitor/Operation ............................................................... 11
4-1. Condition List .............................................................................11
4-2. Measurement List ......................................................................19
4-3. Malfunction List ..........................................................................20
4-4. Filter Sign List ............................................................................22
4-5. AHC List .....................................................................................23
5. Energy Management ..........................................................25
5-1. Energy Use Status .....................................................................25
5-2. Ranking ......................................................................................31
5-3. Target Value Setting ...................................................................34
5-4. Peakcut Control Status ..............................................................36
6. Schedule Settings...............................................................38
6-1. Weekly Schedule .......................................................................40
6-2. Annual Schedule ........................................................................45
6-3. Today's Schedule .......................................................................48
7. Malfunction Log ..................................................................50
7-1. Unit Error/Communication Error .................................................50
8. System Settings..................................................................51
8-1. Date/Time Settings ....................................................................51
8-2. User Registration .......................................................................52
9. Maintenance .......................................................................53
9-1. Send Mail Log ............................................................................53
9-2. Gas Amount Check ....................................................................54
9-3. Outdoor unit status .....................................................................55
9-4. Free Contact List ........................................................................56
9-5. CSV output .................................................................................57
Instruction Book

Advertisement

Table of Contents
loading

Summary of Contents for Mitsubishi Electric EB-50GU-A

  • Page 1: Table Of Contents

    Air Conditioning Control System Centralized Controller EB-50GU-A/EB-50GU-J Instruction Book –Web Browser for System Maintenance Engineer– Contents 1. Introduction ................2 1-1. Terms Used in This Manual ............2 1-2. PC Requirements .................2 2. Setting the Operating Environment ........3 2-1. Setting the IP Address of the PC ..........3 2-2.
  • Page 2: Introduction

    Mitsubishi Electric Corporation’s Centralized Controller EB-50GU-A/EB-50GU-J features functions to allow users to monitor and operate the air conditioning units from a PC over the LAN. This Instruction Book explains how to monitor and operate the units connected to the EB-50GU-A/EB-50GU-J using a Web browser.
  • Page 3: Setting The Operating Environment

    2. Setting the Operating Environment This chapter explains how to make PC settings and Web browser settings to monitor and operate the air conditioning units. 2-1. Setting the IP Address of the PC Follow the instructions below to set the PC's IP address for the Web browser to recognize the EB-50 unit. The PC's IP address must have the same network address as the EB-50's IP address.
  • Page 4 (4) In the [Internet Protocol Version 4 (TCP/IPv4) Properties] window, check the radio button next to [Use the following IP address]. Enter the PC’s IP address (e.g., [192.168.1.101]) in the [IP address] field, and enter the subnet mask [255.255.255.0] (unless otherwise specified) in the [Subnet mask] field.
  • Page 5: Setting The Web Browser

    2-2. Setting the Web Browser Web browser setting varies with the Internet connection type. See the sections below for how to make Web browser settings for different types of Internet connection. To prevent unauthorized access, always use a security device such as a VPN router when connecting the EB-50 to the Internet.
  • Page 6 2-2-2. Dial-up Internet connection To monitor and operate the air conditioning units from a PC that connects to the Internet through a dial-up connection, follow the instructions below to set the environment for the Web browser. (1) Click [Tools] in the menu bar, then click [Internet options]. (2) In the [Internet Options] window, click the [Connections] tab.
  • Page 7 (2) In the [Internet Options] window, click the [Connections] tab. (3) Check the radio button next to [Never dial a connection] in the middle of the window. (4) Click [LAN settings] under [Local Area Network (LAN) settings]. (5) In the [Local Area Network (LAN) Settings] window, check [Bypass proxy server for local addresses], and click [Advanced].
  • Page 8: Logging In To The Web Browser For System Maintenance Engineer

    3. Logging in to the Web Browser for System Maintenance Engineer (1) Enter the web page address in the address field of the Web browser as follows: http ://[IP address of the EB-50]/administrator.html Press the [Enter] key. A login screen will appear. Note: If the IP address of the EB-50 is [192.168.1.1], the web page address is [http ://192.168.1.1/administrator.html].
  • Page 9 (2) Enter the user name and the password in the login screen, and click [Login]. A screen for monitoring the operation conditions will appear. The table below shows the web page addresses for building managers and general users, their respective default user names and passwords, and their accessible functions.
  • Page 10 Encrypting the communication data and logging in to the Web browser (HTTPS connection) EB-50 can encrypt communication data using HTTPS (SSL). When connecting the EB-50 to the LAN that is accessible to the general public, it is recommended that the following settings be made so that the units are monitored and controlled on the encrypted web page.
  • Page 11: Monitor/Operation

    4. Monitor/Operation This chapter explains how to monitor and operate the connected unit groups and to check the measurement data, malfunctioning units, units whose filter sign is triggered, and AHC status. 4-1. Condition List This section explains how to monitor the operation conditions of all groups collectively (see section 4-1-1) or groups per block (see section 4-1-2) and also explains how to operate each group (see section 4-1-3), groups per block (see section 4-1-4), or all groups collectively (see section 4-1-5).
  • Page 12 Item Description Each group icon indicates the operation condition of the group. Move the cursor to the icon to display its group name. Clicking the icon will bring up the operation screen. The icons to indicate the operation conditions are shown below. (1) Air conditioning unit group Error Filter sign ON...
  • Page 13 Item Description (2) LOSSNAY unit (ventilator) group Error Filter sign ON Energy-saving ON Schedule set HOLD ON *1 Whether or not to display the filter sign can be set on the Basic System settings screen, accessible via the Web Browser for Initial Settings. *2 The "Energy-saving ON"...
  • Page 14 4-1-2. Checking the operation conditions of the groups in a given block In the Block display of the Condition List screen, select a block to display the operation conditions (such as operation mode, set temperature, and room temperature) of the air conditioning unit groups, LOSSNAY unit (ventilator) groups, Air To Water (PWFY) unit groups, and general equipment groups in the block.
  • Page 15 Item Description The number of units under the control of EB-50 whose filter sign is currently turned on will Number of units whose filter appear. Clicking " " will bring up the Filter Sign List screen. (See section 4-4.) sign is turned on Note: This item will not appear if the [Filter Sign Display] is set to [OFF] on the Basic System settings screen, accessible via the Web Browser for Initial Settings.
  • Page 16 Air To Water (PWFY) unit: Heating, Heating ECO, Hot Water, Anti-freeze, Cooling Note: Only the operation modes available for the unit model will appear. Note: The Setback mode can be selected on the EB-50GU-A, but not on the EB-50GU-J. Click to adjust the set temperature of the air conditioning unit or the Air To Water (PWFY) unit.
  • Page 17 Browser for Initial Settings. Note: The Hold function cannot be enabled on general equipments. Note: The Hold function can be used on the EB-50GU-A, but not on the EB-50GU-J. Click [ON] or [OFF] to turn on or off the interlocked LOSSNAY unit.
  • Page 18 4-1-4. Operating the units in a given block (1) In the Block display of the Condition List screen, select a block to operate, and click [Batch Operations]. If air conditioner group, LOSSNAY unit (ventilator) group, Air To Water (PWFY) unit group, and general equipment group exist together in the same block, a screen to select a group type will appear.
  • Page 19: Measurement List

    4-2. Measurement List This section explains how to check the measurement data of the temperature sensors, humidity sensors, and metering devices. Click [Monitor/Operation] in the menu bar, and then click [Measurement List] to access the Measurement List screen. Note: An AI controller (PAC-YG63MCA), a commercially available temperature sensor, and a humidity sensor are required to measure the temperature and humidity.
  • Page 20: Malfunction List

    4-3. Malfunction List Click [Monitor/Operation] in the menu bar, and then click [Malfunction List] to access the Malfunction List screen. A list of units that are currently malfunctioning will appear. Error Code List Click to display the list of error codes and their definitions.
  • Page 21 Types of units in error and the units that will stop when errors are reset Types of units in error and the units that will stop Units in error Units that will stop EB-50 None Outdoor unit All indoor units that are connected to the outdoor unit in error Indoor unit Indoor unit in error and all other indoor units in the same group ME (MA) remote controller...
  • Page 22: Filter Sign List

    4-4. Filter Sign List A list of units whose filter sign is turned on can be displayed. Click [Monitor/Operation] in the menu bar, and then click [Filter Sign List] to access the Filter Sign List screen. All Reset Click to reset all filter signs at once.
  • Page 23: Ahc List

    4-5. AHC List On the AHC List screen, the status of input and output ports of each Advanced HVAC CONTROLLER (AHC) can be monitored. Click [Monitor/Operation] in the menu bar, and then click [AHC List] to access the AHC List screen. The port names and their status of each AHC will appear.
  • Page 24 Item Description The number of units under the control of EB-50 whose filter sign is currently turned on will Number of units whose filter appear. Clicking " " will bring up the Filter Sign List screen. (See section 4-4.) sign is turned on Note: This item will not appear if the [Filter Sign Display] is set to [OFF] on the Basic System settings screen, accessible via the Web Browser for Initial Settings.
  • Page 25: Energy Management

    5. Energy Management 5-1. Energy Use Status On the Energy Use Status screen, the energy-control-related status, such as electric energy consumption, operation time, and outdoor temperature, can be displayed in a graph. Operators can check the detailed status of given indoor units by specifying the date to display the data per group, block, or unit address. Also, the status of other indoor units can be displayed at the same time for comparison.
  • Page 26 Item Description Select an item in the top row to display its data in the bar graph, and select an item in the bottom row to display its data in the line graph. Note: The selectable items vary, depending on the items selected in the [Display range] and [Display target] fields.
  • Page 27 Item Description Display items for line graph Display range Display target Display item Address Group Block Outdoor Temp. Target value *1*3 Set Temp. for cool Indoor unit Set Temp. for heat Room Temp. Name of the temperature sensor 1 or humidity sensor 1 (AI controller) Name of the temperature sensor 2 or humidity sensor 2...
  • Page 28 Item Description Click [Download] to export the displayed measurement data in the CSV format. The CSV file name and file format will vary as shown below, depending on the selected date range. ■ File name <When any item in the [Comparison target] field is selected> Date range: Day EM_DailyTrend_[yyyy]-[mm]-[dd]_[Display target]_[YYYY]-[MM]-[DD]_[Comparison target]_ [Bar graph type]_[Line graph type].csv...
  • Page 29 Item Description ■ File format Date Item Format range File Type Month Year dd/mm/yyyy:DD/MM/YYYY Date Month mm/yyyy:MM/YYYY Year yyyy:YYYY "Block" + Block number (Display target)/ Target "Block" + Block number (Comparison target) "Block" + Block number (Display target) (Bar) + "–" + "Time", Display item (Bar), "Block"...
  • Page 30 Item Description ■ File sample Date range: Day 2013/08/19:2012/06/01 Block1/Block5 Time,Block1 - Indoor Unit Electric Energy,Block5 - Indoor Unit Electric Energy,Block1 - Outdoor Temp.,Block5 - Outdoor Temp. 00:00,0.61,0.25,23.2,17.8 01:00,0.65,0.51,23.1,17.6 02:00,0.66,0.48,22.1,18.1 03:00,0.66,0.58,23.3,18.2 04:00,0.63,0.47,24.5,17.5 05:00,0.59,0.39,26.8,19.1 06:00,0.52,0.52,28.1,22.1 23:00,0.59,0.23,23.4,17.1 Date range: Month 2013/08:2012/06 Block1/Block5 Day,Block1 - Indoor Unit Electric Energy,Block5 - Indoor Unit Electric Energy,Target electric energy (kWh),Block1 - Outdoor Temp.,Block5 - Outdoor Temp.
  • Page 31: Ranking

    5-2. Ranking On the Ranking screen, the rankings in electric energy consumption and the fan operation time of given indoor units can be displayed per block, group, and unit in descending order in the bar graph. Click [Energy Management] in the menu bar, and then click [Ranking] to access the Ranking screen. Note: "Energy Management License Pack"...
  • Page 32 Item Description Click [Download] to export the displayed measurement data in the CSV format. The CSV file name and file format will vary as shown below, depending on the selected date range. ■ File name Date range: Day EM_DailyRanking_[yyyy]-[mm]-[dd]_[Display range]_[Ranking graph type].csv Date range: Month EM_MonthlyRanking_[yyyy]-[mm]_[Display range] _[Ranking graph type].csv Date range: Year...
  • Page 33 Item Description ■ File sample Date range: Day 01/23/2013 All blocks Block name,Indoor Unit Electric Energy,Target electric energy (kWh) Block1,25.19,21.2 Block5,19.58,18.13 Unregistered Blocks,17.01,19.73 Block3,11.2,16.9 Block6,6.19,5.24 Block2,5.98,10.96 Date range: Month 01/2013 All blocks Block name,Indoor Unit Electric Energy,Target electric energy (kWh) Download Block1,780.89,657.2 Block5,606.98,562.03...
  • Page 34: Target Value Setting

    5-3. Target Value Setting This section explains how to set the target electric energy consumption values for the entire system for the current year, each month, each day of the week, and each block. The set values will be displayed in the graph on the Energy Use Status screen (see section 5-1) and the Ranking screen (see section 5-2).
  • Page 35 Item Description Enter the target usage ratios of the annual electric energy for each month. Note: Each ratio must be between 0 and 100%. Note: The total of the ratios must be 100%. If the total is not 100%, a window that shows the current total value as shown below will appear and the setting will not be saved.
  • Page 36: Peakcut Control Status

    5-4. Peakcut Control Status This section explains how to check the Peakcut control status. Click [Energy Management] in the menu bar, and then click [Peakcut Control Status] to access the Peakcut Control Status screen. The average electric power consumption (kW) and the control level will appear in the graph. The measurement data can be exported in a CSV format from the screen.
  • Page 37 Item Description ■ File format Item Format File Type Date yyyy/mm/dd Target "Peakcut energy" Measurement item "Time,Power(kW),Control level" hh:mm (1-minute intervals), average electric power consumption, control level 5th– Data Note: The average electric power (kW) values remains unchanged for 30 minutes. *1 The date will appear in the format that has been set on the Basic System settings screen, accessible via the Web Browser for Initial Settings.
  • Page 38: Schedule Settings

    6. Schedule Settings Schedule functions [Weekly 1], [Weekly 2], [Weekly 3], [Weekly 4], [Weekly 5], [Annual], and [Today] are available for use if the "Annual Schedule, Weekly Schedule" license has been registered. Without the license registration, only [Weekly 1] (except the "Seasonal settings") is available for use. Priority Without license registration With license registration...
  • Page 39 Weekly schedule1 (special) Weekly schedule 2 (summer) Weekly Weekly schedule 4 schedule 4 (winter) (winter) Weekly schedule 5 (spring) Weekly schedule 3 (autumn) Note: The figure above shows the setting example of weekly schedules where the date period for each Weekly Schedule is set to the followings. Weekly Schedule 1: Aug 1 - Aug 20 Weekly Schedule 2: Jun 16 - Sep 15 Weekly Schedule 3: Sep 16 - Nov 15...
  • Page 40: Weekly Schedule

    6-1. Weekly Schedule Click [Schedule Settings] in the menu bar, and then click [Weekly 1], [Weekly 2], [Weekly 3], [Weekly 4], or [Weekly 5] to access the Weekly Schedule settings screen. On the Weekly Schedule settings screen, schedules can be set for each day of the week. Note: The "Weekly 1"...
  • Page 41 (1-2) Selecting a block as a target Select [Block] in the Setting Range section. Select a block name, or select one of the group numbers in the block to display the block name automatically. (If the selected group does not belong to a block, the block name will not be displayed automatically.) If air conditioner group, LOSSNAY unit (ventilator) group, Air To Water (PWFY) unit group, and general equipment group exist together in the...
  • Page 42 (1-3) Selecting all groups as a target Select [All Groups] in the Setting Range section. If air conditioner group, LOSSNAY unit (ventilator) group, Air To Water (PWFY) unit group, and general equipment group exist together in the same system, a screen to select a group type will appear. Click one of the group types to set the schedule.
  • Page 43 (4) Setting the contents of the schedule Click [Edit] in the Contents of Schedule section to display the schedule settings screen. Scheduled start time Schedule settings Set the start time to apply to the schedule, set the operations to be scheduled, and then press [OK]. The operations that can be scheduled for air conditioning unit groups are as follows: ON/OFF/Optimized Start, Mode, Set Temp, Air Direction, Fan Speed, and Prohibit Remote Controller Operation.
  • Page 44 (5) Copying a schedule Copy (Day of the week)/Paste To copy the schedule settings of a day to the schedule settings for another day of the week, select the day whose schedule settings are to be copied, click [Copy (Day of the week)], select the day to which the copied schedule settings are to be pasted, and click [Paste].
  • Page 45: Annual Schedule

    6-2. Annual Schedule Click [Schedule Settings] in the menu bar, and then click [Annual Schedule] to access the Annual Schedule settings screen. On the Annual Schedule settings screen, schedules can be set for public holidays or summer vacation. Up to five operation patterns (Pattern 1 through 5) can be set for the 24 months including the current month, and total of 50 days can be allocated to the patterns.
  • Page 46 (3) Setting the contents of the schedule Click [Edit] in the Contents of Schedule section to display the schedule settings screen. Scheduled start time Schedule settings Set the start time to apply to the schedule, set the operations to be scheduled, and then press [OK]. The operations that can be scheduled for air conditioning unit groups are as follows: ON/OFF/Optimized Start, Mode, Set Temp, Air Direction, Fan Speed, and Prohibit Remote Controller Operation.
  • Page 47 (5) Copying a schedule To copy the schedule settings of a pattern to the schedule settings for Copy (Pattern)/Paste another pattern, select the pattern whose schedule settings are to be copied, click [Copy (Pattern)], select the pattern to which the copied schedule settings are to be pasted, and click [Paste].
  • Page 48: Today's Schedule

    6-3. Today's Schedule Click [Schedule Settings] in the menu bar, and then click [Today's Schedule] to access the Today's Schedule settings screen. On the Today’s Schedule settings screen, schedules can be set for the current day without modifying the weekly or annual schedules.
  • Page 49 If the room temperature is measured by the return air temperature sensor on the air conditioning unit, the measured value may not be an accurate representation of the temperature in the room, especially when the air conditioning unit is stopped and the room air is stagnant. When this is the case, use an external temperature sensor (PAC-SE40TSA) or remote controller sensor to measure the room temperature.
  • Page 50: Malfunction Log

    7. Malfunction Log 7-1. Unit Error/Communication Error Click [Malfunction Log] in the menu bar, and then click [Unit Error] to display the last 64 unit errors, or click [Communication Error] to display the last 64 M-NET communication errors. Communication Error Click to display the M-NET communication error log.
  • Page 51: System Settings

    8. System Settings 8-1. Date/Time Settings Click [System Settings] in the menu bar, and then click [Date/Time Settings] to access the date and time settings screen. Set the current date and time, and then click [Save Settings] to send the settings to the EB-50. Note: The date and time settings made on this screen will be reflected on all the units in the M-NET system and on the EB-50 units whose [Time Master] setting is set to [Sub].
  • Page 52: User Registration

    8-2. User Registration On the User Registration screen, the building manager's user name and password can be changed. If the "Personal Web" license is registered, up to 50 general users can be registered, and the groups that each general user is granted access to can be determined. Click [System Settings] in the menu bar, and then click [User Registration] to access the User Registration screen.
  • Page 53: Maintenance

    9. Maintenance 9-1. Send Mail Log Click [Maintenance] in the menu bar, and then click [Send Mail Log] to access the Send Mail Log screen. A list of error notification e-mail that have been sent will appear. Error notification e-mail function is the function to send the error information to the specified e-mail addresses. To use this function, e-mail settings must be configured on the Web Browser for Initial Settings.
  • Page 54: Gas Amount Check

    9-2. Gas Amount Check On the Gas Amount Check screen, operators can check the outdoor units for proper gas refrigerant charge. Click [Maintenance] in the menu bar, and then click [Gas Amount Check] to access the Gas Amount Check screen. Note: Only the outdoor units that support the Gas Amount Check function will appear on the screen.
  • Page 55: Outdoor Unit Status

    9-3. Outdoor unit status On the Outdoor Unit Status screen, operators can check the frequency, high pressure, and low pressure of each outdoor unit. Click [Maintenance] in the menu bar, and then click [Outdoor unit status] to access the Outdoor Unit Status screen.
  • Page 56: Free Contact List

    9-4. Free Contact List This chapter explains how to check the input/output status of the free contacts on the indoor units. Click [Maintenance] in the menu bar, and then click [Free Contact List] to access the Free Contact List screen. Note: The free contact settings must be made on the indoor unit.
  • Page 57: Csv Output

    9-5. CSV output The operation data, such as apportioning parameters, power consumption, and energy management data, can be output in a CSV format from the CSV Output screen. Click [Maintenance] in the menu bar, and then click [CSV output] to access the CSV Output screen. Note: A separate license may be required to use the CSV output function.
  • Page 58 (3) Specify the connection destination and the save destination, and click [Charge Parameters], [Power consumption data], or [Energy management data], referring to the table below. A login screen will appear. Enter the user name and the password, and click [Login]. Note: The building manager or maintenance user can login.
  • Page 59 Item Description Click to download a CSV file of the charge parameters. ■ File name ChargeParameter_[yyyy]-[mm]-[dd]A[Indoor unit address]-[Time period (1–5)].csv Note: The date will appear in the format that has been set on the Basic System settings screen, accessible via the Web Browser for Initial Settings. Note: Time periods 1 through 5 can only be set from TG-2000A.
  • Page 60 Item Description Click to download a CSV file of the power consumption data. ■ File name ChargeParameter_[yyyy]-[mm]-[dd]MCPA[MCP address]-[Time period (1–5)].csv Note: The date will appear in the format that has been set on the Basic System settings screen, accessible via the Web Browser for Initial Settings. Note: Time periods 1 through 5 can only be set from TG-2000A.
  • Page 61 Item Description Click to download a CSV file of the energy management data. The "Select energy management data source" window will pop up. Select a data type and specify the data- acquisition period to acquire the data. Refer to section 9-5-1 "Energy Management Data List" for details about the data that can be output in a CSV format.
  • Page 62 Item Description ■ File output destination [Save destination]\[Serial No.]\OperationalData\EnergyManagementData\[Date] Note: The date will appear in the format that has been set on the Basic System settings screen, accessible via the Web Browser for Initial Settings. ■ File format [Data type: 5-minute intervals] Item Format File Type...
  • Page 63 Item Description [Data type: 30-minute intervals] Item Format File Type Data range Start date + "–" + End date "DateTime,Data1(51),...Data1(100),Data2(51),...Data2(100), Data3(51),...Data3(100),OutdoorTemp(51),...OutdoorTemp(100), CoolSetTemp(1),...CoolSetTemp(50),HeatSetTemp(1),...HeatSetTemp(50), RoomTemp(1),...RoomTemp(50),FanTime(1),...FanTime(50), CoolTime(1),...CoolTime(50),HeatTime(1),...HeatTime(50), ThermoTime(1),...ThermoTime(50),CoolThermoTime(1),...CoolThermoTime(50), HeatThermoTime(1),...HeatThermoTime(50), Item ThermoCount(1),...ThermoCount(50), SaveValue(1),...SaveValue(50),CoolSaveValue(1),...CoolSaveValue(50), HeatSaveValue(1),...HeatSaveValue(50), ApporionedElectricEnergy(1),...ApporionedElectricEnergy(50), MCP1(1),...MCP1(50),MCP2(1),...MCP2(50),MCP3(1),...MCP3(50), MCP4(1),...MCP4(50),MCT1(1),...MCT1(50),MCT2(1),...MCT2(50), AHC1(201),...AHC1(250),AHC2(201),...AHC2(250)" Item Unit ApportionedElectricEnergy ThermoCount, Data1, Data2, Data3 OutdoorTemp, CoolSetTemp, HeatSetTemp, ºC, ºF RoomTemp...
  • Page 64 Item Description [Data type: 1-day intervals] Item Format File Type Data range Start date + "–" + End date "DateTime,Data1(51),...Data1(100),Data3(51),...Data3(100), OutdoorTemp(51),...OutdoorTemp(100),CoolSetTemp(1),...CoolSetTemp(50), HeatSetTemp(1),...HeatSetTemp(50),RoomTemp(1),...RoomTemp(50), FanTime(1),...FanTime(50),CoolTime(1),...CoolTime(50), HeatTime(1),...HeatTime(50),ThermoTime(1),...ThermoTime(50), CoolThermoTime(1),...CoolThermoTime(50), HeatThermoTime(1),...HeatThermoTime(50), Item SaveValue(1),...SaveValue(50),CoolSaveValue(1),...CoolSaveValue(50), HeatSaveValue(1),...HeatSaveValue(50), ApporionedElectricEnergy(1),...ApporionedElectricEnergy(50), TargetElectricEnergy(1),...TargetElectricEnergy(50), MCP1(1),...MCP1(50),MCP2(1),...MCP2(50),MCP3(1),...MCP3(50), MCP4(1),...MCP4(50),MCT1(1),...MCT1(50),MCT2(1),...MCT2(50), AHC1(201),...AHC1(250),AHC2(201),...AHC2(250)" Item Unit ApportionedElectricEnergy, TargetElectricEnergy Data1, Data3 OutdoorTemp, CoolSetTemp, HeatSetTemp, ºC, ºF RoomTemp...
  • Page 65 Item Description [Data type: 1-month intervals] Item Format File Type Data range Start year and month + "–" + End year and month "DateTime,Data1(51),...Data1(100),Data3(51),...Data3(100), OutdoorTemp(51),...OutdoorTemp(100),CoolSetTemp(1),...CoolSetTemp(50), HeatSetTemp(1),...HeatSetTemp(50),RoomTemp(1),...RoomTemp(50), FanTime(1),...FanTime(50),CoolTime(1),...CoolTime(50), HeatTime(1),...HeatTime(50),ThermoTime(1),...ThermoTime(50), CoolThermoTime(1),...CoolThermoTime(50), HeatThermoTime(1),...HeatThermoTime(50), Item SaveValue(1),...SaveValue(50),CoolSaveValue(1),...CoolSaveValue(50), HeatSaveValue(1),...HeatSaveValue(50), ApporionedElectricEnergy(1),...ApporionedElectricEnergy(50). TargetElectricEnergy(1),...TargetElectricEnergy(50), MCP1(1),...MCP1(50),MCP2(1),...MCP2(50),MCP3(1),...MCP3(50), MCP4(1),...MCP4(50),MCT1(1),...MCT1(50),MCT2(1),...MCT2(50), AHC1(201),...AHC1(250),AHC2(201),...AHC2(250)" Item Unit ApportionedElectricEnergy, TargetElectricEnergy Data1, Data3 OutdoorTemp, CoolSetTemp, HeatSetTemp,...
  • Page 66 Item Description [Data type: 1-year intervals] Item Format File Type Date range Start year + "–" + End year "DateTime,Data1(51),...Data1(100),Data3(51),...Data3(100), FanTime(1),...FanTime(50),CoolTime(1),...CoolTime(50), HeatTime(1),...HeatTime(50),ThermoTime(1),...ThermoTime(50), CoolThermoTime(1),...CoolThermoTime(50), HeatThermoTime(1),...HeatThermoTime(50),SaveValue(1),...SaveValue(50), Item CoolSaveValue(1),...CoolSaveValue(50), HeatSaveValue(1),...HeatSaveValue(50), ApporionedElectricEnergy(1),...ApporionedElectricEnergy(50) TargetElectricEnergy(1),...TargetElectricEnergy(50), MCP1(1),...MCP1(50),MCP2(1),...MCP2(50),MCP3(1),...MCP3(50), MCP4(1),...MCP4(50)" Item Unit ApportionedElectricEnergy, TargetElectricEnergy Energy management Data1, Data3 Measurement data unit FanTime, CoolTime, HeatTime, ThermoTime,...
  • Page 67 9-5-1. Energy Management Data List Table 9-1 below summarizes the energy-control-related items that can be output in a CSV format, their measurement units, and their data ranges for each data type. Table 9-2 below summarizes how many months/years worth of data each CSV file can contain. Table 9-1 Data items Data type (intervals) Measurement...
  • Page 68: License Registration For Optional Functions

    10. License registration for optional functions This chapter explains how to register a license for optional functions. Please ask your dealer for more details on the optional functions and how to purchase a license number. Note: The current date and time settings are required for license registration. Refer to section 8-1 for date and time settings.
  • Page 72 This product is designed and intended for use in the residential, commercial and light-industrial environment. The product at hand is based on the following EU regulations: • Electromagnetic Compatibility Directive 2004/108/EC • Restriction of Hazardous Substances 2011/65/EU Please be sure to put the contact address/telephone number on this manual before handing it to the customer.