Dlink Settings - GE MDS TransNEXT NET9L Technical Manual

Table of Contents

Advertisement

3.3.8.6 Ippl.connection_timeout [0-65535]
This attribute specifies the connection timeout in milliseconds for all modes. The timeout is the
maximum time the connection can remain idle before dropping the connection. 0 is reserved as a special
value to mean do not apply a connection timeout. Default is 0.
3.3.8.7 ippl.keepAlive ["on" or "off"]
This attribute enables connection keep alive. Default is "off".

Dlink settings

The Dlink attribute group contains settings associated with DLINK diagnostic. DLINK is used for
Network Management (PulseNET, Field Network Manager, and similar tools). In TransNEXT DLINK
operation is expected to occur via TCP on the Ethernet port.
>cfg get dlink
{
enabled: "on",
type: "node",
tcp_access: "off",
connection_timeout: 0,
tcp_port: 30020,
trend_resp_win: 120
}
NOTE
Dlink.trend_resp_win is reserved for future use.
3.3.9.1 dlink.enabled ["on" or "off"]
This attribute enables dlink network-wide diagnostics transactions. Default is "off".
NOTE
To address security concerns, TransNEXT normally ships with DLINK disabled. It is
important to set dlink.enabled to "on" for each unit, prior to deployment if this operation is
desired.
3.3.9.2 dlink.type [<dlink type choice>]
This attribute specifies the radio's operational characteristics for network-wide diagnostics. Valid dlink
type choices include "node", "root", "repeater", "peer", and "gate". Default is "node"
NOTE
Selections "repeater", "peer", and "gate" are reserved for special use.
NODE is the most common setting, and the default. This is the basic system radio device-type. Typically,
the radio network is comprised of nodes and one root. Non-intrusive diagnostics can only be conducted
from the root node.
ROOT is limited to one, and only one, per network (including units associated through Extension units.)
The root is the focal point of network-wide diagnostics information. The root is the only radio through
which non-intrusive diagnostics can be conducted. This value should be set on Master (radio.mode "m").
3.3.9.3 dlink.tcp_access ["on" or "off"]
This attribute enables dlink network-wide diagnostics transactions. Default is "off".
42
MDS TransNEXT Technical Manual
MDS 05-7280A01, Rev. A

Advertisement

Table of Contents
loading