D1M 15 MULTIMETER USER MANUAL
29
CFG>UNT>HOMEPAGE
LED
LED is used to indicate the speed of energy consumption. It can be configured to output Total Active
Import Energy(IPEN), Total Active Export Energy(EPEN), Total Reactive Import Energy(IQEN), Total
Reactive Export Energy(EQEN), Total Apparent Import Energy(ISEN) and Total Apparent Export
Energy(ESEN).
The pulse width can be configured between 10ms and 990ms, and it can be set via the HMI and
communication.
The pulse width should satisfy the following formula:
Pulse width≤1000/(Energy∗Factor)ms
The pulse factor range between energy and pulses is 1 to 99999999 pulse per energy, the energy type can
be set as Active Energy, Reactive Energy or Apparent Energy, magnitude and unit can be MWh/MVarh/
MVAh.