Download Print this page

Mitsubishi Electric 800 Series Instruction Manual page 4

Safety stop function
Hide thumbs Also See for 800 Series:

Advertisement

Safety stop function with SIL 3 certification
The Mitsubishi Electric FR-A800/F800 inverters now comply with safety integrity level 3 (SIL 3) of the IEC
EC61508:2010 functional safety standard.
• Target models
Mitsubishi Electric FR-A800/F800 inverters
• Change of the compliance
The Mitsubishi Electric FR-A800/F800 inverters now comply with SIL 3.
ISO13849-1:2008 Category 3/PLd
Safety
IEC62061:2005 / IEC61800-5-2:2007 /
performance
IEC61508 SIL2
(Standards)
IEC61800-5-2:2007 Stop category 0
• Schedule
Check the SERIAL number indicated on the inverter rating plate or package.
For the products manufactured in Japan, this change has been made sequentially from the June 2018 production.
For the products manufactured in China, this change has been made sequentially from the July 2018 production.
SERIAL
number
Country
of origin
Warning
 The misuse of safety function leads to personal injury or death, property damage, or economic loss.
To ensure that the system complies fully with requirement of safety, make a system-level risk
assessment. Mitsubishi Electric Corporation. cannot assume responsibility for any system to
comply with safety standards.
NOTE
• The safety stop function of the Mitsubishi Electric FR-A800-R2R, FR-A800-ELV and FR-A800M inverter
meets the following standards and categories.
• Safety Integrity Level (SIL) 2
ISO13849-1:2015 Category 3/PLd
IEC62061:2021 / IEC61800-5-2:2016 / IEC61508:2010 SIL2
IEC61800-5-2:2016 Stop category 0
4
GENERAL DESCRIPTION
Table 1 Compliance with SIL 3
Before change
Figure 2 Rating plate example
The SERIAL consists of one symbol, two characters indicating the
production year and month, and six characters indicating the
control number.
The last digit of the production year is indicated as the Year, and
the Month is indicated by 1 to 9, X (October), Y (November), or Z
(December).
ISO13849-1:2015 Category 3/PLe
IEC62061:2021 / IEC61800-5-2:2016 /
IEC61508:2010 SIL3
IEC61800-5-2:2016 Stop category 0

Symbol Year Month Control number
SERIAL
After change

Advertisement

loading

This manual is also suitable for:

Fr-a800Fr-f800Fr-a800-r2rFr-a800-elvFr-a800m