5.2 Preparing Cables

Table 5-1 Cable description (S: cross-sectional area of the AC cable conductor; S
area of the ground cable conductor)
No.
Cable
1
DC power
cable (multi-
core)
DC power
cable (single
core)
2
Ground
[1]
cable
3
FE
communicatio
ns cable
4
AC power
cable (multi-
core)
AC power
cable (single
core)
Note [1]: The value of S
are made of the same material. If the materials are different, ensure that the conductor cross-
sectional area of the ground cable produces a conductance equivalent to that of the area S/2. The
specifications of the ground cable are subject to this table or calculated according to IEC
60364-5-54.
Issue 05 (2022-06-30)
Type
Two-core outdoor cable
and M12 OT/DT terminal
Single-core outdoor cable
and M12 OT/DT terminals
Single-core outdoor
copper cable and M10
OT/DT terminals
CAT 5E outdoor shielded
network cable (internal
resistance ≤ 1 ohms/10
m) and the shielded RJ45
connector
Three-core (L1, L2, L3)
outdoor cable and M12
OT/DT terminals (L1, L2,
L3)
Single-core outdoor cable
and M12 OT/DT terminals
is valid only if the conductors of the ground cable and AC power cable
p
Copyright © Huawei Technologies Co., Ltd.
Conductor
Outer
Cross-Sectional
Diameter
Area Range
30–60 mm
2
70–185 mm
15–35 mm
2
50–185 mm
S
≥ S/2
-
p
4.5–7.5 mm
2
0.2 mm
30–65 mm
2
70–240 mm
15–35 mm
2
70–240 mm
5 Electrical Connections
: cross-sectional
p
Source
Prepared
by the
customer
Prepared
by the
customer
Prepared
by the
customer
The cable
delivered
with the
device is
1.2 m
long. You
can also
prepare a
cable
according
to site
requireme
nts.
Prepared
by the
customer
Prepared
by the
customer